5-19
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02
Service Manual - DUO Series
5.9
DUO WNG (9+12): Room A + Room B
5.9.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
DATA
ENTERING AIR WB/DB ID COIL ( °C)
15/21
17/24
19/27
21/29
23/32
15
(1)
TC
6.25 6.47 6.63 6.78 6.89
SC
4.58 4.78 4.97 5.09 5.18
PI
1.47 1.47 1.47 1.48 1.48
20
(1)
TC
6.05 6.37 6.58 6.73 6.88
SC
4.49 4.74 4.94 5.08 5.17
PI
1.59 1.60 1.60 1.61 1.62
25
TC
5.72 6.18 6.50 6.69 6.85
SC
4.38 4.64 4.90 5.04 5.13
PI
1.72 1.73 1.75 1.76 1.77
30
TC
5.35 5.83 6.29 6.52 6.71
SC
4.24 4.51 4.79 4.93 5.02
PI
1.86 1.88 1.90
1.92 1.93
35
TC
4.95 5.38
5.93
6.23 6.52
SC
4.03 4.32
4.68
4.82 4.91
PI
2.00 2.04
2.07
2.09 2.10
40
TC
4.50 4.90 5.35
5.85 6.15
SC
3.80 4.09 4.43 4.57 4.66
PI
2.16 2.19 2.23 2.26 2.28
46
TC
3.91 4.27 4.70 5.19 5.59
SC
3.50 3.75 4.04 4.18 4.27
PI
2.36 2.40 2.45 2.49 2.51
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible
Capacity,
kW
PI –
Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OU –
Outdoor