2-9
PRODUCT DATA SHEET
Revision Y05-01
Service Manual - DNC Series
DNC 1255
Model
Ceiling Mounted
Installation method
Heating
Cooling
Units
Characteristic
44700
42500
Btu/hr
13096
12460
W
Capacity
3970
4390
W
Total input
3.3
2.84
W/W
COP
400V/50Hz/3
Power supply (voltage, cycle, No of phases)
3 x 10.4
3 x 11.6
A
Rated current
3 x 16
A
Circuit breaker rating
Plug Fan x 1
Fan type & qty.
5
0
0
5
5
0
830
RPM
Fan speed (HI-M-LO)
1
23
0
1
350
2000
m³/hr
720
795
1176
CFM
Airflow (HI-M-LO)
2
0-80
Pa
Static Pressure
54.8
56
59.3
dBA
Noise Power** (HI-M-LO)
47.5
49.7
53.3
dBA
Noise Pressure* (HI-M-LO)
4.7
l/h
Dehumidification
16
mm
Condensate drain tube I.D
1025
mm
W
Dimensions
760
mm
D
300
mm
H
44
Kg
Weight
1125x975x360(Unit)+1180x870x180(Frame)
mm
Package dimensions
7
units
Stacking height
7
units
Units per palet
I
N
D
O
O
R
U
N
I
T
Capillary Tube
Refrigerant control
SCROLL ZR54
Compressor type & model
Axial x 2
Fan type & qty.
1125
RPM
Fan speeds
4150
m³/hr
2440
CFM
Airflow (std. conditions)
57/65
dBA
Noise Pressure*/ Noise Power
900
mm
W
Dimensions
350
mm
D
970
mm
H
95
Kg
Weight
1020x985x406
mm
Packing dimensions
2
units
Stacking height
6
units
Units per palet
R22
Refrigerant
Charge for 7.5 meter pipes length
O
U
T
D
O
O
R
U
N
I
T
16
mm
Condensate drain tube I.D
3/8”
in.
liquid
3/4”
in.
suction
25
m
height difference
Connection between units
50
m
tubing length
T
U
B
E
S
LCD Remote Control
Operation control type
2x1500
W
Heating elements
8”,10”,12”
Ducts
Crankcase heater 60W,3PH Protector
Others
A
C
C.
* Noise pressure tested at 1m distance from unit
** Noise power for ducted units measured at air outlet side
Grams
2660