www.elector-water-treatment.com
elector – Electrochemical Water Treatment for Heating Systems
The installation of the elector device into the system should always be done via the elector connection set. The
connection set is tailored to the device and provides its function. The connection-set differs in accordance to
installation in full flow and in the bypass.
Please refer to the data sheet which kind of installation is suitable for your elector.
5.1 Connection-Set Full Flow – elector XS5, elector S10-V
The connection set contains:
(1) Ball valve
(2) Elbow fitting
(3) Double nipple
(4) T-piece
(5) Drain valve
(6) Ball valve
(7) Filter magnet
5.2 Connection-Set Bypass – elector S10-B, elector M25, elector L60, elector XL130, elector XL+
The required components vary depending on the installation.
On site must be provided (depending on the
installation):
(1) Weld on socket or t-piece for elector inlet
connection, min. 1“.
(2) possibly 1“ feed pump with ball valve.
(12) Weld on socket of t-piect for elector outlet.
The connection set contains:
(3) Ball valve.
(4) T-pice.
(5) Drain valve.
(6) Reduction (if necessary).
(7) Double nipple.
(8) Blind plug.
(9) Elbwo 90°.
(10) Water meter (rotatable) with fitting.
(11) Regulating valve with automatic flow control
and deaerator.
When installing the elector corrosion protection system in the bypass, the flow must be regulated. The flow rate
can be checked and documented via the provided water meter.
elector Type
S10-B
M25
L60
XL130
XL+300
XL+500
Flow rate l/min
2
5
10
20
50
100
5.3 Additional Components
A useful additional components is the installation of a microbubble separator.
Chapter 5 - Assembly of the Connection-Set
IN
OUT
1
7
2
2
6
3
4
5
Outlet
Inlet
1
2
3
4
5
6
8
10
11
12
7
9
elector
Anode mA
m
3
0 1
2
3
4
5
6
7
8
9
0 1
2
3
4
5
6
7
8
9
0 1
2
3
4
5
6
7
8
9
0 1
2
3
4
5
6
7
8
9
0 0 0 0 0
min. Distance
400 mm