ELAN3
SNMP Ethernet Controller
Sensor no.
- Sequence number of the temperature sensor.
Name
– Temperature sensor name that might be included in temperature trap message.
Min Value
– Minimum temperature level threshold resulting in temperature trap message delivery to the preset destination IP ad-
dress(-es) when exceeded. Value range is
-55... 125 °C
. Default value is
10 °C..
Max Value
– Maximum temperature level threshold resulting in temperature trap message delivery to the preset destination IP ad-
dress(-es) when exceeded. Value range is
-55... 125 °C
. Default value is
25 °C.
.
5.1.7. Outputs
This section is intended for output C1 and C2 control.
The ELAN3-SNMP device comes equipped with 2 open collector outputs C1 and C2 designed for electricalal appliance connection. Nor-
mally, outputs can be used to open/close garage doors, activate lights, heating, watering and much more. When output turns ON, the
ELAN3-SNMP triggers any equipment or relay connected to it (see
2.3. Wiring Diagrams
).
When input Z4 is operating in Digital or Analog mode, output C2 will not be available. In such case C2/Z4 terminal can not be used as
open-collector output. In order to use C2/Z4 terminal as open-collector output, disable input Z4. For more details on input configuraiton,
please refer to
5.1.5. Inputs
.
NOTE:
Output C2 and input Z4 DO NOT operate simultaneously..
12
The output can be turned ON or OFF by selecting a corresponding output status ON or OFF from the drop down list and clicking the
Save
button afterwards. By default, output C1 and C2 are turned OFF.