Valid for firmware revision 1.00 and above
CIM-130&136-KLRV MAN - EN – p.
18 of 16
NOTICES
Only for starting and surveillance of the diesel motor pump and stops it if there are anomalies in the parts controlled by
probes.
It has been designed to be installed also on the machine.
Warning:
adhere closely to the following advice
-
Connect always following the wiring diagram.
-
Each technical operation must take place on the motor pump unit with the engine stopped and with terminal 50
of the starter motor disconnected.
-
Check that the line loading and the consumption of the connected equipment are compatible
-
with the described technical characteristics.
-
Install in such a way that there is always adequate heat disposal.
-
Always install under other equipment which produces or spreads heat.
-
Make sure that no copper conductor cuttings or other waste material fall inside the control unit.
-
Never disconnect the battery terminals with the engine running.
-
Never use a battery charger for the emergency start-up, this could damage the control unit.
-
To protect the safety of persons and the equipment, before connecting an external battery charger, disconnect
the electrical plant terminals from the battery poles.
THIS CONTROL UNIT IS NOT SUITABLE FOR OPERATING IN THE FOLLOWING CONDITIONS:
- Where the environmental temperature is outside the limits indicated in the Technical Data.
- Where the air pressure and temperature variations are so rapid as to produce exceptional condensation.
- Where there are high levels of pollution caused by dust, smoke, vapour, salts and corrosive or radioactive particles.
- Where there are high levels or heat from radiation caused by the sun, ovens or the like.
- Where attacks from mould or small animals are possible.
- Where there is the risk of fire or explosions.
- Where the control unit can receive strong vibrations or knocks.
ELECTROMAGNETIC COMPATIBILITY
This control unit functions correctly only if inserted in plants which conform with the CE marking standards; it meets the
exemption requirements of the standard EN61326-1 but it cannot be excluded that malfunctions could occur in extreme
cases due to particular situations.
The installer has the task of checking that the disturbance levels are within the requirements of
the standards.
CONDUCTION AND MAINTENANCE
The following maintenance operations should be performed every week:
-
check that the indicators function;
-
check the batteries;
-
check that the conductors are tight, check the condition of the terminals.
UNLESS WE MAKE A WRITTEN DECLARATION STATING THE CONTRARY, THIS CONTROL UNIT IS NOT SUITABLE FOR USE
AS A CRITICAL COMPONENT IN EQUIPMENT OR PLANTS RESPONSIBLE FOR KEEPING PERSONS OR OTHER LIVING BEINGS
ALIVE.
YOUR ELECTRICAL TECHNICIAN CAN ASK US ANYTHING ABOUT THIS CONTROL UNIT BY TELEPHONING ONE OF OUR
TECHNICIANS