14
Operating manual VARION® C-POWER 50.0 / 09.2019
Assembly
5.2.2 Installation room
The installation room must meet the following
requirements:
B
The installation room must comply with the effective
applicable laws and regulations for boiler rooms
(e.g. in Germany, the ordinance for heat-producing
appliances (Feuerstättenverordnung)).
B
The substrate on which the generation unit is to be
installed must be flat, even, solid, dry and load-bearing.
B
The ambient temperature must be between
+5 °C and +30 °C.
B
The room height must be at least 2,400 mm from the
installation surface.
B
The system must be protected against frost and the
elements.
The following are not permitted:
B
Installation on floating screed.
B
Operation of tumble dryers in the same room.
B
Storage of explosive or highly flammable materials
(e.g. paper, paints, petrol) within the installation
location.
B
Use of aggressive substances (e.g. sprays, solvents,
chlorinated cleaning agents, paints, adhesives) in the
vicinity of the system.
If the system is installed in vaulted cellars or bare smooth-
walled rooms (hard-walled), there is a risk of noise and
sound resonance.
The system must be positioned so that the following
requirements are fulfilled:
B
None of the system’s ventilation or extraction devices
may be blocked or closed.
B
The emergency stop switch must always be accessible.
Space requirement (VARION® C-POWER 50.0 Standard,
VARION® C-POWER 50.0 High temperature)
> 700
> 700
> 700
> 700
2587
822
1756
Space requirement (VARION® C-POWER 50.0 Calorific value)
> 700
> 700
> 700
> 700
3806
969
1781
The minimum distance (> 700 mm on all sides) must be
maintained.
Minimum distance for maintenance work:
B
600 mm free space above the system.
B
300 mm free space next to the control cabinet.
If the minimum distances are not maintained:
A
Contact the manufacturer.
Summary of Contents for VARION C-POWER 50.0
Page 1: ...Made in Germany Operating manual Combined heat and power unit VARION C POWER 50 0 09 2019...
Page 41: ...41 Operating manual VARION C POWER 50 0 09 2019 Appendix...
Page 42: ...42 Operating manual VARION C POWER 50 0 09 2019...
Page 43: ...43 Operating manual VARION C POWER 50 0 09 2019...