check that the refractory lining of the door has not been damaged;
-
check that the burner draught tube has been correctly sealed
-
check that the discharge valves are closet and the system cut -off valves are completely open;
-
ensure that the fuel is available and that fuel controls are open;
-
Ensure that the electric motors of the burner fan and circulation pumps are running in t he
correct rotation;
-
Check that the water treatment system (if any) works properly;
-
Start the circulation pumps and ensure that the water runs homogeneously (the plant must be
de-aerated).
FIRST START UP
After performing the preliminary checks, perform the following operations to start the boiler:
-
set the boiler thermostat(s) on the control panel; 60 to 90°C, according to the type of plant;
-
set the master switch to "on";
-
press the main control panel switch (the button light will come on).
The boiler will perform an ignition phase and, once started, will remain on until the set temperatures
have been reached.
Operation will be automatic from now on.
FIRST START UP AND FURTHER CHECKS
Once the boiler has been started, check that it stops and then starts a gain by:
-
altering the boiler thermostat setting;
-
operating the main switch on the main control panel.
Check the seal on all the gaskets on the water and fume side; they must be further tightened while
hot in order to guarantee a perfect seal.
This operation is of fundamental importance for the gaskets of the door, of the burner plate and of
the smokebox to prevent leakage of toxic and therefore hazardous combustion fumes into the boiler
room.