Trinox Floor Standing Shell and Tube Boiler
21 L344
©
Elco UK 04/07/2012
REMEDY:
-
Turn off the burner, do not pour water and do not open the door : wait until
the ambience temperature is restored before performing any operation.
FAULT: water on the floor near the smoke box (condensate).
REMEDY:
-
check the probes have been correctly positioned. Ensure that the boiler regulation thermostat
has been correctly regulated and works properly (min. 60°C):
-
ensure that the smoke box discharge is connected to a collecting basin;
-
check that the anti-condensate pump (if any) is properly set and works well;
-
check that return water temperature to the plant is no lower than 50 °C.