background image

ELM-961 

 

instruction manual

IM441-U v0.6 

pag. 5

 

DESCRIPTION FRONT PANEL–  OPERATORS 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

    

 

 

 

 

 

 

 
 
 
 
LEGEND: 

A

:        push-button  for  the  visualization  of  electrical parameters of three-phase system with the corresponding LED 

indication. In modality programming (SETUP) it’s used to confirm the parameter set. 

B

:        push-button for the selection of the electrical parameter to be displayed on display F. In modality programming 

(SETUP) it’s used to increase the value of the parameters to set. 

C

:        push-button for the selection of the electrical parameter to be displayed on display G. In modality programming 

(SETUP) it’s used to reduce the value of the parameters to set. 

D

:        LED bar for the indication of the electrical parameter displayed on display F. 

E

:        LED bar for the indication of the electrical parameter displayed on display G. 

F

:        3 displays for the visualization of electrical measures of every phase. 

When 

Σ

L LED is ON, only the main display will be active showing the three-phase system value of the electrical 

measure selected. 
LED k and M show the eventual multiplying factor (k = kilo=x 1.000, M =Mega= x 1.000.000) 
If it’s selected with the C key the display indicates also the values of the active, reactive and apparent energy 
counters. If it’s selected with the A and B keys the display indicates the maximum and average values. 

G

:       display for the visualization of the electrical measure indicated in LED E (energy counters excluded). 

The voltage values are referred to the three-phase system. 
The k LED displays the reading in kilo (x 1000). 
If it’s selected with C key the display indicates the type of the energy displayed. If it’s selected with A and B keys, 
the display indicates the type of average of maximum values. 

A+C

:when pressing simultaneously the instrument pass to the following menu: 

- instrument programming (SETUP) 
- energy counters and peak values deleting (RESET) 
- digital outputs programming (SET  DO1;  SET  DO  2) (only for version with digital output) 
- hour counter programming (HR_) 
- I/O diagnostic page 

A+B

:when  pressing simultaneously the instrument pass to the visualization of average and maximum values stored. 

 

MENU OF INSTRUMENT PROGRAMMING (SETUP) 

To enter in SETUP it’s necessary to press at the same time A and C keys, on the F display will appear the message 
SETUP. Pressing the A key on the G display will appear the message SET   that will  remain always displayed during the 
set of each parameter to highlight the SeTUp phase in running. 
The set values will be keep also in absence of auxiliary power supply. 

Summary of Contents for ELM-961

Page 1: ...internal CT digital output in alternative to the serial port serial port in alternative to the digital output power supply different from standard version current input 1A MEASURED PARAMETERS paramete...

Page 2: ...400V 300 500V phase to phase 175 290V phase neutral 230V 175 290V phase to phase 130 170V phase neutral L2 L3 phase to phase power supply 110V 85 145V phase to phase 50 85V phase neutral 230V 300 500V...

Page 3: ...IRES ELM on line with 3 wires without neutral or with neutral not supplied the N terminal must not be connected L1 S1 P1 S1 L2 P1 L3 N S1 S2 P1 P2 LOAD I1 I3 VL1 VL2 VL3 INSERTION ON THREE PHASE LINE...

Page 4: ...N ON SINGLE PHASE LINE I1 I2 S1 I3 VL1 VL2 VL3 if the multimeters are used on single phase line the measure are referred at the L3 phase The others data displayed relatives at value of three phase sys...

Page 5: ...the values of the active reactive and apparent energy counters If it s selected with the A and B keys the display indicates the maximum and average values G display for the visualization of the electr...

Page 6: ...kVAr pulse version with digital output 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse seT TPL Increase from 100 to 500 mS in step by 100 mS Decrease version with digital output seT ID ADR In...

Page 7: ...decrease it press the C key To confirm it press the A key The average time is the time used to calculate the average parameters avg and the maximum demand maxD Programming of the energy visualization...

Page 8: ...rd when required by the instrument at the enter of the setup use the A B and C keys as the same way done previously The menu is cyclic After the last setting the instrument go back to the first page o...

Page 9: ...ALR LO With ALR SYS 123 the digital output will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum value of t...

Page 10: ...the set SET THE HIGH AND THE LOW THRESHOLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with...

Page 11: ...ime the B key to select the parameter and the A key to confirm it SET THE THRESHOLD Subsequently it s necessary to set the threshold using the B to increase and C to decrease keys Confirm with A key I...

Page 12: ...all the measures appear on the L3 display Visualization section 2 At the same way of the section 1 press the C button to select the parameter that can be displayed and indicated from E LED The voltag...

Page 13: ...s max maxD avg I L1 max avg I L2 max avg I L3 max avg phase currents maximum of average phase currents max demand max maxD avg W max avg VAr max avg VA max avg three phase power maximum of average thr...

Page 14: ...se speed Not shielded connection As shown in the diagram it is necessary to place a serial RS232 485 converter between the RS232 PC s outlet and the instrument s it s necessary to insert a line termin...

Page 15: ...ELM 961 instruction manual IM441 U v0 6 pag 15 DIMENSIONS ELM 961 96 9 56 cut panel 96 96 R3 92 90 92 20...

Page 16: ...1 to 400 0 current inputs from 0 02 to 5A permanent overload 30 from external TA with secondary 5A primary programmable from 5 to 10000A auto consumption 0 5VA INPUTS OUTPUTS digital outputs Two outpu...

Reviews: