background image

ELCO spa - ELK 39 - OPERATING INSTRUCTIONS - Vr. 02 - ISTR 06262 - PAG. 12

 

AL1H  –  HIGH  ALARM  AL1:  Alarm  AL1  high  threshold  when  the 
alarm is a band type or maximum set of AL1 alarm threshold when 
the alarm is low or high type. 
HAL1  -  ALARM  AL1  HYSTERESIS:  Asymmetrical  semi-band 
relative to alarm AL1 threshold which defines the deactivation value 
of alarm AL1. 
AL1d  –  ACTIVATION  DELAY  OF  ALARM  AL1:  This  permits 
definition of  alarm delay activation AL1 when the delay function on 
par. “Ab1” is activated. 
AL1i  –  ALARM  AL1  ACTIVATION  IN  CASE  OF  MEASUREMENT 
ERROR: This permits a definition of measurement error conditions, 
i.e whether the alarm has to be active ("yES") or not ("no"). 
 
GROUP  “LbA”  (PARAMETERS  RELATIVE  TO  THE  LOOP 
BREAK  ALARM):  this  contains  the  parameters  relative  to  the 
Loop  Break  alarm  (control  loop interruption), which intervenes 
when,  for  any  reason  (short-circuit  of  a  thermocouple,  load 
interruption, etc) the control loop is interrupted.  
OLbA
  –  OUTPUT  WHERE  THE  LOOP  BREAK  ALARM  IS 
ADDRESSED: This defines to which output the LOOP BREAK alarm 
has to be addressed.  
LbAt  –  TIME  NECESSARY  TO  ACTIVATE  THE  LOOP  BREAK 
ALARM  :    Delay  time  to  the  intervention  of  the  Loop  Break  alarm. 
The  alarm  intervenes  when  the  output  power  remains  at  100%  for 
the time programmed on this parameter (in sec.) 
 
GROUP  “ 

]

rEG” (PARAMETERS RELATIVE TO THE CONTROL): 

this contains the parameters relative to control functions. 
Cont  
–  CONTROL  TYPE:  This  permits  selection  of  one  of  the 
possible  control  modes  offered  by  the  instrument  :  PID  (Pid),  
ON/OFF  with  asymmetrical  hysteresis  (On.FA),    ON/OFF  with 
symmetrical hysteresis (On.FS), Neutral Zone ON/OFF (nr). 
Func  –
  FUNCTIONING  MODE  OUTPUT  1rEG:  this  permits  one  to 
decide  whether  the  control  output  1rEG  has  to  carry  out  a  reverse 
action, as for example a Heating process ("HEAt") or a direct action, 
as for example a Cooling process ("CooL"). 
HSEt  –ON/OFF  CONTROL  HYSTERESIS:  Semi-band  relative  to 
the Set Point which defines the activation and deactivation values of 
the control output/s in case of  ON/OFF control (On.FA, On.FS, nr). 
CPdt  –  COMPRESSOR  PROTECTION  DELAY  TIME:  The  delay 
time is counted starting from the last 2rEG output switch off , when 
it’s  used  as  Neutral  zone  control  mode,  during  which  the  output  is 
kept  in  off  state.  The  output  will  be  switched  on  when  the 
temperature regulator requires it at this time is elapsed. The function 
in deactivated programming "CPdt" = OFF. 
Auto  –  AUTO-TUNING  FAST  ENABLE  :  this  parameter allows one  
to  decide  how  Auto-tuning  has  to  be  carried  out.  The  possible 
selections are : 
=  1  –  if  auto-tuning  is  desired  automatically,  each  time  the 
instrument is switched on, on the condition that the process value is 
lower  (with  “Func”  =HEAt)  than  [SP-  |SP/2|]  or  higher  (with  “Func” 
=CooL) than [SP+ |SP/2|]. 
=  2  –  if  auto-tuning  is  desired  automatically,  the  next  time  the 
instrument is switched on, on the condition that the process value is 
lower  (with  “Func”  =HEAt)  than  [SP-  |SP/2|]  or  higher  (with  “Func” 
=CooL)  than  [SP+  |SP/2|],  and  once  the  tuning  is  finished, the par. 
“Auto” is automatically swapped to the OFF state  
=  3    -  if  manual  auto-tuning  is  desired,  by  selecting    par.  “tunE”  in 
the  main  menu  or  by  correctly  programming  key  “U”  as  “USrb”  = 
tunE.  In  this  case  the  auto-tuning  starts  without  any  control  on  the 
process  value  condition.  It  is  recommended  to  use  this  option, 
starting the auto-tuning when the process value is as far as possible 
from  the  Set  Point  because,  in  order  to  feature  the  Auto-tuning 
FAST  with  its  best  performances  ,  it  is  preferable  to  respect  this 
condition. 
=  4    -  if  it’s  desired  to  activate  the  autotuning  automatically  at  the 
end of programmed Soft-Start cycle. The Autotuning will start at the 
condition  that  the  process  value  is  lower  (with  “Func”  =HEAt)  than 
[SP- |SP/2|] or higher (with “Func” =CooL) than [SP+ |SP/2|]. 
= OFF - Autotuning disabled. 
When it’s occurring an Autotuning cycle, led AT blinks. 
SELF  –  SELF-TUNING  ENABLE:  Parameter  used  to  enable  (yES) 
or disable (no) the Self-tuning function. Once the function has been 

enabled,  the  Self-tuning  has  to  be  started  by  selecting  item  “tunE”, 
in the main menu, or through key U properly programmed (“USrb” = 
tunE).When the Self-tuning function is active, led AT is permanently 
lit, and all the PID parameters ("Pb", "Int", "dEr", ecc.) are no longer 
visualised. 
Pb  –  PROPORTIONAL  BAND:  Width  of  the  band  around  the  Set 
Point within which the proportional control is performed. 
Int  –  INTEGRAL  TIME:  Integral  time  to  be  programmed  in  the  PID 
algorithm, expressed in sec.  
dEr – DERIVATIVE TIME: : Derivative time to be programmed in the 
PID algorithm, expressed in sec.  
FuOc  -  FUZZY  OVERSHOOT  CONTROL:  Parameter  that  permits 
the  elimination  of  the  variable  over-shoots  at  the  start  up  of  the 
process  or  at  the  changing  of  the  Set  Point.  A  low  value  of  this 
parameter reduces the overshoot while a high value increase it.  
 tcr1 – CYCLE TIME OF OUTPUT 1rEG : Cycle time of output 1rEG 
with PID control mode, expressed in sec.. 
Prat – POWER RATIO 2rEG / 1rEG : Parameter where it is possible 
to program the power ratio between the element controlled by output 
2rEG  (ex.Cooling)  and  the  element  controlled  by  output  1rEG  (ex. 
Heating) in case of PID double action control. 
tcr2 - CYCLE TIME OF OUTPUT 2rEG : Cycle time of output 2rEG 
with PID double action control mode, expressed in sec.. 
rS -  MANUAL RESET: Power Offset added to the power increase of 
the  proportional  term,  in  order  to  eliminate  the  error  when  it  is  not 
present  the  integral  value.  This  parameter  is  only  visualised  when  
“Int” =0. 
Parameters  relative  to  the  ramps,  allowing  the  Set  Point  to  be 
reached in a predetermined time.  
Furthermore,  once  the  first  Set  (SP1)  has  been  reached,  it  is 
possible  to  have  automatic  switching  to  the  second  Set  (SP2) 
after  a  programmable  time,  thus  obtaining  a  simple  thermal 
cycle (functions available for all the control types)   
SLor
  –  GRADIENT  OF  RISE  RAMP:    Gradient  of  rise  ramp  to  be 
carried  out  when  the  process  value  is  lower  than  the  active  Set 
Point, expressed in unit/minute. 
Programming the parameter = InF the ramp is not active. 
dur.t  -  DWELL  TIME:  Dwell  time  of  the  Set  Point  SP1  before  the 
automatic switching to SP2 (expressed in hrs. and min.) 
Using this parameter, once the first Set (SP1) has been reached, it 
is  possible  to  have  automatic  switching  to  the  second  Set  (SP2) 
after a programmable time, thus obtaining a simple thermal cycle. 
Programming the parameter = InF the function is not active. 
SLoF  -  GRADIENT  OF  FALL  RAMP:    Gradient  of  fall  ramp  to  be 
carried  out  when  the  process  value  is  higher  than  the  active  Set 
Point, expressed in unit/minute. 
Programming the parameter = InF the ramp is not active. 
Parameters  relative  to  the  Soft-Start  function,  which  allows 
limitation  of  control  power,  when  the  instrument  is  switched 
on, for a predetermined time. This function is only available for 
PID control. 
St.P
  -  SOFT  START  POWER:  If  parameter  “SSt”  is  programmed 
with a value other than OFF, this is the power given as output at the 
instrument switch on, for the time “SSt”.  
Practically  speaking,  the  instrument  works  in  manual  condition  and 
switches to automatic control at the elapsing of time “SSt”. 
If  instead  par.  “St.P”  =  OFF  and  a  value  is  set    on  par.  “SSt”  at 
switch  on,  the  power  calculated  by  the  PID  controller  is  divided  by 
the time “SSt”, in order to calculate a ramp. The output power starts 
from  0  and  is  progressively  increased,  according  to  the  calculated 
ramp,  until  the  time  “SSt”  is  reached  or  until  the  power  overcomes 
the power calculated by the PID controller. 
SSt  -  SOFT  START  TIME  (for  PID  control  only):  Duration  time  in 
hours and min. of the Soft-Start described on pa. “St.P”.  
To disable the Soft-Start function set par. “SSt” = OFF. 

 

GROUP    “ 

]

PAn”  (PARAMETERS  RELATIVE  TO  THE  USER 

INTERFACE)  :  This  contains  the  parameters  relative  to  the  key 
U and display functions.
 
Usrb – KEY U FUNCTION : Decides which function is associated to 
key U. The possible selections are : 
= noF : no function 

Summary of Contents for ELK 39

Page 1: ...ROL 4 5 SINGLE ACTION PID CONTROL 4 6 DOUBLE ACTION PID CONTROL 4 7 AUTO TUNING AND SELF TUNING FUNCTIONS 4 8 REACHING OF SET POINT AT CONTROLLED SPEED AND AUTOMATIC COMMUTATION BETWEEN TWO SET POINTS...

Page 2: ...g speed increases in order to allow the desired value to be reached rapidly Once the desired value has been reached by pushing key P it is possible to exit by the fast programming mode or it is possib...

Page 3: ...of the controller During automatic control it is possible to visualize the control power on the display by pushing key UP The range of the power values goes from H100 100 of the output power with reve...

Page 4: ...0 2 10 V Depending on the model using par SEnS it s possible to select the type of input probe which can be for thermocouples J J K CrAL S S or for infrared sensors serie ELCO IRTC1 with linearizatio...

Page 5: ...w value SP HSEt Vice versa in case of direct action or cooling Func CooL it deactivates the output when the process value reaches SP HSEt in case of symmetrical hysteresis or SP in case of asymmetrica...

Page 6: ...ontrol monitoring and the continuous calculation of the parameters during control Both functions automatically calculate the following parameters Pb Proportional Band tcr1 Cycle time of the output 1rE...

Page 7: ...n only works through PID control and allows the limitation of control power when the instrument is switched on for a programmable period of time This is useful when the actuator driven by the instrume...

Page 8: ...condition the alarm is not activated It will be activated only when the process value is in non alarm conditions and then back in alarm conditions ALARM DELAY the alarm output may behave in two diffe...

Page 9: ...ument is equipped with a connector that allows the transfer from and toward the instrument of the functioning parameters through the device ELCO KEY01 with 5 poles connector This device it s mainly us...

Page 10: ...1 28 AL1d Activation delay of alarm AL1 OFF 9999 sec OFF 29 AL1i Alarm AL1 activation in case of measuring error no yES no Group LbA parameters relative to Loop Break Alarm Par Description Range Def...

Page 11: ...e condition occurs in case of over range or probe breakage Ur the condition occurs in case of under range or probe breakage Our the condition occurs in case of over range or under range or probe break...

Page 12: ...led AT blinks SELF SELF TUNING ENABLE Parameter used to enable yES or disable no the Self tuning function Once the function has been enabled the Self tuning has to be started by selecting item tunE i...

Page 13: ...mmed on par OPE and activates the desired alarms if the relative parameters ALni have been programmed yES 6 2 CLEANING We recommend cleaning of the instrument with a slightly wet cloth using water and...

Page 14: ...02 0 F NTC 103 AT2 SEnS ntc 50 110 C 58 230 F 50 0 110 0 C 58 0 230 0 F 0 20 mA SEnS 0 20 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 4 20 mA SEnS 4 20 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999...

Reviews: