background image

ELCO spa - ELK 39 - OPERATING INSTRUCTIONS - Vr. 02 - ISTR 06262 - PAG. 7

 

 
To activate the SELF-TUNING function proceed as follows 
1) Program and activate the desired Set Point. 
2) Program par. "Cont" =Pid. 
3)  Program  par.  "Func"  according  to  the  process  to  be  controlled 
through output 1rEG. 
4)  Program  an  output  as  2rEG  if  the  instrument  controls  a  dual-
action plant  
5) Program par. "SELF" = yES 
6) Exit from the parameter programming. 
7) Connect the instrument to the controlled plant. 
8)  Activate  Self-tuning  selecting  par.  “tunE”  in  the  main  menu  (or 
by correctly programming key “U”). 
When  the  Self-tuning  function  is  active,  the  led  AT/ST  is 
permanently  lit  up  and  all  the  PID  parameters  ("Pb",  "Int",  "dEr", 
etc.) are no longer visualized. 
 
To  stop  the  Auto-tuning  cycle  or  deactivate  the Self-tuning function 
select  one  of  the  control  types  :  "rEG",  "OPLO"  or  "OFF"  from  the 
menu  “SEL”.  If  the  instrument  is  switched  off  during  Auto-tuning  or 
with  the  Self-tuning  function  activated,  these  functions  will  remain 
activated the next time it is switched on. 
 
4.8  -  REACHING  OF  THE  SET  POINT  AT  CONTROLLED  SPEED 
AND  AUTOMATIC  SWITCHING  BETWEEN  TWO  SET  POINTS 
(RISE RAMP, FALL RAMP AND DWELL TIME)
 
All  the  parameters  referring  to  the  ramps  functioning  are  contained 
in the group 

]

rEG”. 

It  is possible to reach the set point in a predetermined time (in any 
case longer than the time the plant would naturally need). This could 
be  useful  in  those processes (heating or chemical treatments, etc.) 
where the set point has to be reached gradually, in a predetermined 
time. 
Once the instrument has reached the first Set Point (SP1) it is 
possible to have automatic switching to the second Set Point (SP2) 
after a set time, thus obtaining a simple automatic thermic cycle. 
These functions are available for all the programmable controls (PID 
single and double action, ON/OFF and Neutral Zone ON/OFF). 
The function is determined by the following parameters :  
"SLor"  -  Gradient  of  rise  ramp    (Process  value  <  Set  point) 
expressed in unit/minute  
"SLoF"  -  Gradient  of  fall  ramp  (Process  value  >  Set  point) 
expressed in unit/minute. 
"dur.t" – Dwell time of Set Point SP1 before automatic switching to 
Set Point 2 SP2 (expressed in hrs. and min.). 
The  functions  are  deactivated  when  the  relative  parameters  are  = 
InF. 
When the Set Point value is changed or at switch on, the instrument 
automatically determines which of the two values “SLor” or “SLoF” it 
has to use.  
Note:  In  case  of  PID  control,  if  Auto-tuning  is  desired  whilst  the 
ramp  function  is  active,  this  will  not  be  carried  out  until  the  tuning 
cycle has been completed. 
It  is  therefore  recommended  that  Auto-tuning  be  started  avoiding 
activating  the  ramp  function  and,  once  the  tuning  is  finished, 
deactivate Auto-tuning  (“Auto” = OFF), program the desired ramps 
and, if it automatic tuning is desired, enable the Self-tuning function. 

 

Examples with starts from values lower than SP and with decreasing 
of SP. 
 
4.9 - SOFT-START FUNCTION 
All  the  parameters  referring  to  the  Soft  -Start  functioning  are 
contained in the group 

]

rEG”. 

The  Soft-Start  function  only  works  through  PID  control  and  allows 
the  limitation  of  control  power  when  the  instrument  is  switched  on, 
for a programmable period of time. 
This  is  useful  when  the  actuator,  driven  by  the  instrument,  may  be 
damaged  excess  power  supplied  when  the  application  is  not  yet  in 
the normal rating. (ex. for certain heating elements).  
The function depends on the following parameters : 
 “St.P” – Soft-Start power 
“Sst” – Soft-Start time (expressed in hh.mm) 
The possible function modes are the following : 
1) If both parameters are programmed with values other than OFF, 
when  switched  on  the  instrument  gives  an  output  power  as 
programmed  on  par.  “St.P”  for  the  time  programmed  on  par.  “SSt”. 
Practically,  the  instrument  works  in  manual  condition  and  switches 
to automatic control at the elapsing of time “SSt”. 
It is advisable not to program a power “St.P” that is too high as the 
function  is  not  deactivated  when  the  automatic  control  power  is 
found to be lower than the programmed one. 
2) If par. “St.P” = OFF and a value is set on par. “SSt” , at the switch 
on, the power calculated by the PID controller is divided by the time 
“SSt”,  in  order  to  calculate  a  ramp.  The  output  power  starts  from  0 
and  is  progressively  increased,  depending  on  the  calculated  ramp, 
until  the  “SSt”  time  is  reached  or  until  the  power  overcomes  the 
power calculated by the PID controller. 
To disable the Soft-Start function simply program par. “Sst” = OFF 
Whenever,  a  measurement  errors  occurs  during  the  Soft-Start 
execution,  the  function  is  interrupted  and  the  instrument  gives  an 
output power as programmed on par. “OPE”. 
If the measurement is restored, the Soft-Start is still deactivated. 
If  it’s  desired  to  activate  the  Autotuning  with  Soft-Start  set  par. 
“Auto”=4.  
The  Autotuning  will  start  automatically  at  the  end  of  programmed 
Soft-Start cycle at the condition that the process value is lower (with 
“Func” =HEAt) than [SP- |SP/2|] or higher (with “Func” =CooL) than 
[SP+ |SP/2|]. 
 
4.10 – ALARM FUNCTIONING (AL1)
 
 
4.10.1 – ALARM OUTPUT CONFIGURATION 
The  alarm  is  depending  on  the  process  value  (AL1)  and  before  to 
set  his  functioning  it’s  necessary  to  establish  to  which  output  the 
alarm has to correspond to. 
First  of  all  it’s  necessary  to  configure,  in  the  parameters  group 

]

Out”,    the  parameters  relative  to  the  outputs  required  as  alarm 

(“O1F”  ,  “O2F”)  programming  the  parameter  relative  to  the  desired 
output as follows : 
=  ALno  if  the alarm output has to be ON when the alarm is active, 
while it’s OFF when the alarm is not active. 
=  ALnc  if  the  alarm  output  has  to  be  ON  when  the  alarm  is  not 
active, while it’s OFF when the alarm is active. 
=  ALni  if  the  alarm  output  has  to  be  ON  when  the  alarm  is  not 
active, while it is OFF when the alarm is active but with reverse led 
indication (led ON= alarm OFF). 
Have  now  access  at  the  group  

]

AL1”,  and  program  on  par. 

“OAL1” , to which output the alarm signal has to be sent. 
The alarm functioning is instead defined by parameters : 
"AL1t " – ALARM TYPE 
"Ab1" – ALARM CONFIGURATION 
“AL1” – ALARM THRESHOLD  
“AL1L”  –  LOW  ALARM  THRESHOLD  (for  band  alarm)  OR 
MINIMUM  SET  OF  AL1  ALARM  THRESHOLD  (for  low  or  high 
alarm) 
“AL1H”  -  HIGH  ALARM  THRESHOLD  (for  band  alarm)  OR 
MAXIMUM  SET  OF  AL1  ALARM  THRESHOLD  (for  low  or  high 
alarm) 
“HAL1” - ALARM HYSTERESIS 
“AL1d” – ALARM ACTIVATION DELAY (in sec.) 

Summary of Contents for ELK 39

Page 1: ...ROL 4 5 SINGLE ACTION PID CONTROL 4 6 DOUBLE ACTION PID CONTROL 4 7 AUTO TUNING AND SELF TUNING FUNCTIONS 4 8 REACHING OF SET POINT AT CONTROLLED SPEED AND AUTOMATIC COMMUTATION BETWEEN TWO SET POINTS...

Page 2: ...g speed increases in order to allow the desired value to be reached rapidly Once the desired value has been reached by pushing key P it is possible to exit by the fast programming mode or it is possib...

Page 3: ...of the controller During automatic control it is possible to visualize the control power on the display by pushing key UP The range of the power values goes from H100 100 of the output power with reve...

Page 4: ...0 2 10 V Depending on the model using par SEnS it s possible to select the type of input probe which can be for thermocouples J J K CrAL S S or for infrared sensors serie ELCO IRTC1 with linearizatio...

Page 5: ...w value SP HSEt Vice versa in case of direct action or cooling Func CooL it deactivates the output when the process value reaches SP HSEt in case of symmetrical hysteresis or SP in case of asymmetrica...

Page 6: ...ontrol monitoring and the continuous calculation of the parameters during control Both functions automatically calculate the following parameters Pb Proportional Band tcr1 Cycle time of the output 1rE...

Page 7: ...n only works through PID control and allows the limitation of control power when the instrument is switched on for a programmable period of time This is useful when the actuator driven by the instrume...

Page 8: ...condition the alarm is not activated It will be activated only when the process value is in non alarm conditions and then back in alarm conditions ALARM DELAY the alarm output may behave in two diffe...

Page 9: ...ument is equipped with a connector that allows the transfer from and toward the instrument of the functioning parameters through the device ELCO KEY01 with 5 poles connector This device it s mainly us...

Page 10: ...1 28 AL1d Activation delay of alarm AL1 OFF 9999 sec OFF 29 AL1i Alarm AL1 activation in case of measuring error no yES no Group LbA parameters relative to Loop Break Alarm Par Description Range Def...

Page 11: ...e condition occurs in case of over range or probe breakage Ur the condition occurs in case of under range or probe breakage Our the condition occurs in case of over range or under range or probe break...

Page 12: ...led AT blinks SELF SELF TUNING ENABLE Parameter used to enable yES or disable no the Self tuning function Once the function has been enabled the Self tuning has to be started by selecting item tunE i...

Page 13: ...mmed on par OPE and activates the desired alarms if the relative parameters ALni have been programmed yES 6 2 CLEANING We recommend cleaning of the instrument with a slightly wet cloth using water and...

Page 14: ...02 0 F NTC 103 AT2 SEnS ntc 50 110 C 58 230 F 50 0 110 0 C 58 0 230 0 F 0 20 mA SEnS 0 20 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 4 20 mA SEnS 4 20 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999...

Reviews: