Vv CM78N_C02_1.ING.doc 28/05/2009 page 3/6
BASIC SETTING
CM78N-C02 can be configured by the user to fit to different operational modes.
The configuration is performed as follows:
Press the key
F
to access the configuration phase. The display will show
Ch.SEt.
Digit the key sequence
R – Arrow 2 - Arrow 4
– within 5 seconds. The display will
show:
F:XXXXX
Now you can enter the configuration code.
The configuration code is composed according to the table hereunder: each code
position corresponds to a column of the table; each option corresponds to a line of
the table. The setting is made by pressing the arrow key corresponding to the digit to
be modified until reaching the number corresponding to the required function.
F.XXXXX BASIC SET-UP
OPERATING MODE
Count type
Functional
Inputs Polarity
Decimal Digits
Input IN3
Function
0
Position visualiser
Bidirectional x 4
NPN
No one
Count block
1
Position visualiser with
alarms
Bidirectional x 1
PNP
1
Display block
2
Absolute/relative position
visualiser with alarms
Monodirectional
up-counter
2
3
Monodirectional
down-counter
3
SETTING CONFIRMATION
After entering the required configuration code press
F
to confirm and access the setting of the
operating functions
specific for the
chosen operational mode.
SPECIFIC SETTINGS
This phase can also be accessed pressing
F
and, when the display shows
Ch.Set,
entering the key sequence
Arrow 1, Arrow 6,
Arrow 2.
The setting is made by pressing the arrow key corresponding to the digit to be modified until reaching the number corresponding to the
required function.
According to the chosen operational mode you can meet three possible situations:
OPERATIONAL MODE 0
C.XX
–
OPERATIONAL MODE 0 – SPECIFIC SET-UP
LOAD BY KEYBOARD
LOAD BY INPUT
0
Disabled
On the closure state
1
Enabled
On the closure front
OPERATIONAL MODE 1
C.XXX
–
OPERATIONAL MODE 1 – SPECIFIC SET-UP
LOAD BY KEYBOARD
RELAY OPERATION
END STROKE SETTING
LOAD SETTING
0
Disabled Steady
outputs
Free
Free
1
Enabled
Pulse timed outputs
Under set-up key
Under set-up key
2
Under constants key
Under constants key
OPERATIONAL MODE 2
C.XXXX
–
OPERATIONAL MODE 2 – SPECIFIC SET-UP
COMPARING MODE FACTOR 2 DECIMALS
RELAY OPERATION
STROKE END SETTING
0
Absolute record
No one
Steady outputs
Free
1
Relative record
1
Timed pulse outputs
Under set-up key
2
2
Under constants key
3
3
SETTING CONFIRMATION
After entering the required set-up press
F
to confirm. If the chosen selection involves the parameters entering under SET-UP key the
parameter setting phase is accessed; otherwise you switch to the main display page.
Key Arrow 1