ELAP CM78N Operating Manual Download Page 2

Vv CM78N_C02_1.ING.doc 28/05/2009                                                     page 2/6 

 

OPERATING SPECIFICATIONS 

POWER ON 

At power on the display shows the current operational mode and 
the identification of the sofware version. 

DEFAULT CONFIGURATION 

(See the tables at page 3)

 

If not differently specified in the order, the instrument is supplied 
with the following configuration: 

Basic setting: 

F. 00000 

Corresponding to: 

Position visualiser, count x 4, NPN inputs 
polarity, no decimal digits, input IN3 
function=count block 

Specific setting: 

C. 00 

Corresponding to: 

LOAD by keyboard enabled, LOAD by 
input on the closure state 

POSITION VISUALISATION 

It is assumed by convention that the default display unit is mm. 
This is in no way obligatory. Keeping to the convention makes it 
possible to use the mm/inch conversion facility. 

PULSES COUNT 

For all the selectable operational modes the instrument main 
function is counting the pulses provided by the connected position 
transducer. 
The options relating to this function are, in detail: 

 

bidirectional count x 4 

 

bidirectional count - direct 

 

monodirectional up-count 

 

monodirectional down-count 

Bidirectional Count 

The bidirectional count is obtained by exploiting the phase 
difference between the transducer channels to discriminate 
between up- and down-count. 

Direct Count/Count x4 

One bidirectional count pulse includes 

a complete pulse on both 

count channels. 

Incrementing the count by one for each complete 

pulse gives as a result the 

direct count. 

That means that using the 

direct count mode the count value obtained for each encoder turn 
corresponds to the transducer ppr number. 
Each 

double-channel count has four fronts

: 2 ascent fronts and 2 

descent fronts. Counting all the fronts gives as a result a 

quadrupled count

 number in respect to the encoder ppr number. 

When calculating the multiplying factor it is necessary to pay 
attention to the selected count mode. 

Monodirectional Up- or Down-count 

One single channel is used in this case, therefore the signals 
cannot be used to discriminate the count direction. 
The up or down direction count is chosen in the configuring 
phase. The monodirectional count is always direct (x1). 
 

MULTIPLYING FACTOR 

The total value of the inputs counted according to the selected 
mode is stored into the instrument count record. The count record 
value is not displayed directly; the display value is the result of 
the following calculation. 

Display value = count record value x  multiplying factor

 

This allows to display the counted pulses in the required 
measuring unit. 
The multiplying factor value can range between 0.01 and  
9.99999. 
 
 

MULTIPLYING FACTOR CALCULATION 

To define the multiplying factor value it is necessary to know the 
following data: 

A

:  value that must be displayed for each encoder rotation. 

The value must be expressed in the resolution unit used 
for the visualisation (see the example) 

B

:   number of the encoder pulses 

C

:   set count mode (x1, x4) 

The value of the multiplying factor is the result of the following 
calculation: 

 
 Factor 

= A / (B x C) 

 
To obtain that the visualised resolution is not beneath the real 
resolution (B x C) must be 

 A. 

EXAMPLE

 

Suppose you avail on 50 mm diameter measuring wheel  coupled 
to a 500 ppr encoder. You wish to visualise the displacement with  
0.1 mm resolution. 
The value to be displayed for each encoder revolution 
corresponds to the measuring wheel development expressed in 
millimeter-tenths. Therefore the wheel diameter must be 
expressed in mm-tenths for the calculation of the wheel 
develoment. 

Data

 

A

 = 500  x  3.1415 

B

 = 500 

C

 = x4 

 

 

Factor

 = (500  x  3.1415)/(500  x  4) = 0.785375 

ALARM THRESHOLDS 

Both  

operational mode 1

 and 

2

 make available two alarms, which 

are enabled by comparison in respect to the displayed count 
record value. In the setting phase the alarms are indicated as 

positive stroke end

 and 

 negative stroke end

. The former is 

enabled for  value 

 the count record, the latter for value 

 than 

the count record. 
The alarms enabling is signalled by the relevant relay outputs 
switching. 
The operating mode of the two outputs can be selected: either 
steady or by timed pulse. In case 

timed pulse 

outputs are 

selected the required excitation time must be set in the relevant 
parameter menu. 
REMARK: For 

operational mode 2

 the alarms can be enabled 

either in comparison with the absolute record or with the relative 
record (see the specific settings).  
 

ABSOLUTE/RELATIVE COUNT RECORD DISPLAY 

CM78N-C02 avails on  two separate count records: the absolute 
count record and the relative count record. 
The absolute record is shown in the main display page; a starting 
value (LOAD value) can be loaded into the absolute record by the 
relevant terminal box input. The absolute record is usually 
referred to the machine zero reference and the LOAD value is 
only entered at the machine initializing phase. 
Pressing the key

 P2

 switches the visualisation to the relative 

count record. In this phase a flashing dot appears on the display 
second digit left. 
The relative count record is an auxiliary visualization and can be 
reset by pressing the key 

R

.  The relative count record is usually 

referred to the working piece zero reference and is reset 
whenever it is necessary. 

 
 
 
 
 
 
 

Summary of Contents for CM78N

Page 1: ...starting the configuring operations MANUAL STRUCTURE Pages 1 to 3 of the present manual relate to the instrument general working mode Pages 4 to 6 relate to the operating way of each operational mode The paragraph Operating specifications page 2 gives details about the instrument configurations SUMMARY page Technical specifications 1 Introduction 1 Operational modes description 1 Operating specifi...

Page 2: ...unted pulses in the required measuring unit The multiplying factor value can range between 0 01 and 9 99999 MULTIPLYING FACTOR CALCULATION To define the multiplying factor value it is necessary to know the following data A value that must be displayed for each encoder rotation The value must be expressed in the resolution unit used for the visualisation see the example B number of the encoder puls...

Page 3: ...ng of the operating functions specific for the chosen operational mode SPECIFIC SETTINGS This phase can also be accessed pressing F and when the display shows Ch Set entering the key sequence Arrow 1 Arrow 6 Arrow 2 The setting is made by pressing the arrow key corresponding to the digit to be modified until reaching the number corresponding to the required function According to the chosen operati...

Page 4: ...er key cancels the operation INPUTS OUTPUTS The instrument is equipped with three inputs performing the following operations IN1 load see paragraph specific settings IN2 mm inch display switch IN3 count block or visualisation block see par basic settings Outputs are not used in this operational mode LOAD BY INPUT Closing input IN1 the LOAD value is displayed If the function load on the closure sta...

Page 5: ...g operations IN1 load IN2 mm inch display switch IN3 count block or visualisation block IN1 LOAD BY INPUT Closing input IN1 the LOAD value is displayed If the function load on the closure state was selected the pulses count is blocked until input IN1 is opened again IN2 mm inch CONVERSION Closing inpunt IN2 the display indication is switched form mm to inch The inch displayed value has one decimal...

Page 6: ...N3 count block or visualisation block IN1 ABSOLUTE VALUE LOADING On the input IN1 closure front the LOAD value is entered into the absolute count record IN2 MULTIPLYING FACTOR 1 2 SELECTION Closing input IN2 the display indication is switched from Displayed RECORD COUNT x FACTOR 1 to Displayed RECORD COUNT x FACTOR 2 The number of displayed decimals corresponds to the setting Factor 2 decimals see...

Page 7: ......

Reviews: