16
For more information: paragraph 2.5.11
p. 12.
Such user change can be disabled during configuration.
5.6 Advanced settings
The installer can set advanced settings using BrowserOne
software.
5.6.1 Dialler block at disarming
Users can require to block phone communications (voice
and digital) caused by sectors disarming.
This function is available in
System Options
menu in
BrowserOne.
If dialler block is removed, the phone dialler will activate
when the first event generated after the removal occurs.
5.6.2 Limits to dialler activations
Installers can program the control unit so that it limits the
number of events that trigger the dialler.
When the max number is reached, the voice/SMS dialler ig-
nores other calls until the next day.
This function is available in
Telephone Dialler
menu in
BrowserOne.
Limits refer to events, and not to calls: the amount of
calls can be higher if events cause several calls. More-
over, the limit refers only to voice dialler and not digital
dialler.
For
Low battery
and
No Supervision
events a limit to the
number of calls they may generate (both voice and digital)
can be set using the software application.
In addition, such events will activate the dialler only if there
are no discharged battery memories for the relevant device.
5.6.3 Disable arm/disarm commands
Installers can disable arm/disarm commands via SMS texts
or voice communications (not digital ones) for each single
user.
This function is available in
Users
menu in BrowserOne.
6
TEMPERATURE MONITORING
HERCOLA series units are equipped with a temperature de-
tector measuring the temperature inside the housing.
6.1 Temperature thresholds
The installer can set two thresholds, one minimum and one
maximum:
• when the temperature goes from minimum to maximum
threshold the "Maximum Temperature" event will be
generated.
• when the temperature goes from maximum to minimum
threshold the "Minimum Temperature" event will be
generated.
Such events can be used to activate the on-board relay or
an external one.
6.2 A-B temperatures management
A more advanced temperature control can be re-
alised using output functions and alarm/pre-alarm
thresholds (in
BrowserOne
: page Temperature, tab
Management of A-B temperatures
).
The installer can set four thresholds with corresponding
events: two for high temperature (Pre-alarm A and Alarm A),
and two for low temperature (Pre-alarm B and Alarm B.)
The installer can set an output to activate when the temper-
ature reaches one of the thresholds and to reset when the
temperature falls again within threshold ranges set.
If the temperature is not over/under thresholds set, the out-
put can be reset also by users in the two following ways:
It is required the installer has set one output with
Control of A-B temperatures
function associated to a
SX
sector key.
Reset from keypad
– Key in user code.
– Press SX sector key.
Reset via SMS
– Send SMS command
S.X
(see chapter 10
p. 21).
Example
If S3 key has been associated to the function, the output will
reset:
• with the user code keyed in and followed by S3 key, or
• sending an SMS text with
S.3
6.3 Calibration
The temperature detected by the sensor is affected by
the heat generated by electronic components inside the
housing.
For a correct detection, it may be necessary to calibrate the
detector.
Use
TEMP CALIBR.
option in user menu (see paragraph
2.5.7
p. 11).
If the temperature displayed is x°C below environment tem-
perature, set a + x°C adjustment.
If the temperature sensor has not been calibrated, the