SELV/LPS-conform voltage as per IEC 60950-1/EN60950-1/VDE0805-1. Please observe the
instructions for SELV voltages according to the legal instructions at the beginning of this operating
manual.
Figure 2: VDC connection terminal
Note: Please tighten the screws and check that all connections are stable.
Note: Please note the corresponding cable cross-section of at least 0.5 mm
2
or 12~ 24 AWG during
wiring.
2.5.5
Failure relay connection
Between the terminals labeled
there is a potential-free fault relay contact. The relays act as
alarm receivers and can be connected in the software with different alarm triggers. Depending on
the configuration, they activate, for example, in case of a voltage failure, RJ45 port error or a LWL
port error. In the software, the relay is marked relay 1.
Note: The capacity of the relay contact amounts to 25 VDC (1A) of 60 VDC (0.3A).