background image

Monitoring system
EKO-KE2 

Description

The EKO-KE2 control and monitoring system is in-
tended for use in the automatic monitoring and per-
formance testing of up to two fire/smoke dampers, 
smoke dampers or pressure relief dampers with 24 V 
damper motors and various types of smoke detector.

EKO-KE2 uses a built-in transformer to provide 

power to both actuators and smoke detectors. The 
unit has been developed using the latest technology 
and meets the requirements for a monitoring system 
laid down in the Swedish National Board of Housing, 
Building and Planning’s General Guidelines, as well 
as the applicable standards of VVS AMA 09.

Function – Indication

EKO-KE2 is equipped with nine LEDs that indicate 
the operating status of the control unit and each of 
the damper groups, plus a test button for damper 
performance testing and a reset button to reset 
alarms. When the system is starting up, EKO-KE2 
detects which damper inputs are connected. The 
LEDs for “Normal” and “Alarm/Error” flash during 
startup. This takes around five minutes.

Reset

Alarms or errors are reset manually using the reset 
button on the front of the monitoring unit. The  
monitoring system is reset automatically once  
the external alarm has been reset. (Optional, see 
page 3)

Automatic performance testing/time 

The EKO-KE2 control and monitoring system perfor-
mance tests connected dampers 10 hours after the 
unit has been supplied with voltage or after the manual 
test has been conducted; the unit is then performance 
tested every 48 hours. This displacement is to avoid 
performance testing taking place during the daytime.  
The option to conduct performance testing at other 
time intervals or at other times can be enabled by con-
necting an external timer to “Trigg in” and setting DIP 
switch 4 to the ON position. Once the performance 
test is complete, which takes around four minutes, the 
green operating LED and green LED at every damper 
indicate normal position. If the test has failed, it will be 
repeated once more in order to minimise failure alarms. 
If this test also fails, a failure alarm will be generated.

Manual performance test

The dampers can be performance tested by pressing 
the test button for automatic function test located on 
the front of the monitoring unit. The internal clock is 
reset for every performance test, which means that 
this function can also be used to change the time the 
performance test takes place.

Electrical installation

The unit is intended for permanent installation and 
must be preceded by an all-pole power switch with 
a gap of at least 3 mm.

2020-03

1 (5)

EKOVENT AB, Mejselgatan 7, SE-235 32 Vellinge, Sweden
Tel +46 40 42 16 00, [email protected], www.ekovent.com

Summary of Contents for EKO-KE2

Page 1: ...ee page 3 Automatic performance testing time The EKO KE2 control and monitoring system perfor mance tests connected dampers 10 hours after the unit has been supplied with voltage or after the manual test has been conducted the unit is then performance tested every 48 hours This displacement is to avoid performance testing taking place during the daytime The option to conduct performance testing at...

Page 2: ...ashing Operation power on Red 2 Non flashing Fire alarm Yellow 3 Non flashing Detector loop error Yellow 3 Flashing Damper error Red Yellow 2 3 Flashing Service alarm detector Green 4 Non flashing Normal mode Red 5 Non flashing Alarm mode Red Yellow Green 1 2 3 Non flashing Night closing dampers When the system is starting up EKO KE2 detects which damper inputs are connected EKO KE2_2011 measure 1...

Page 3: ...tor is present even if it is not selected In such case flashes red and yellow even during startup 2 Night closing Connected Disconnected 14 15 Alarm input 2 If night closing is not selected no jumper is required at the input If night closing is activated both red and yellow light Concluded with a manoeuvring operation 3 Post cooling Connected Disconnected 4 5 Releases buzzer alarm 1 seven minutes ...

Page 4: ...er motor 24 V 20 21 22 23 1 S4 2 S1 S2 S6 Inkopp Ex KE2 Spj2_2011 EKO KE2 Damper motor 24 V Damper motor 24 V 16 17 18 19 1 2 S2 S6 4 conductor cable 4 conductor cable S1 1 2 S4 S2 S6 S1 S4 2 dampers Series connection example Damper 1 Damper 2 Damper group 1 2020 03 4 5 EKOVENT AB Mejselgatan 7 SE 235 32 Vellinge Sweden Tel 46 40 42 16 00 info ekovent se www ekovent com ...

Page 5: ...gsexempel EKO KE2 kanaldetektor EKO RE i serie EKO RE Channel detector 2 1 5 6 7 2 2 kOhm EKO RE Channel detector 2 1 5 6 7 EKO RE Channel detector 2 1 5 6 7 EKO RE Channel detector 2 1 5 6 7 24 VAC separate supply for any auxiliary fan Smoke detectors connected in series When several smoke detectors are connected in series a terminating resistor must only be fitted to the last detector in the loo...

Reviews: