7
EKOVENT AB
We reserve the right to make changes
2020-12
2
2
≤100
Assembly instruction EKO-BSV3 in distribution box
Maintenance EKO-BSV3
External and internal control
When cleaning or at least every three years,
check the protective cover and insert. Also
check that the corrosion protection is intact.
– Unscrew the star handle (2) and re-
move the insert from the spiro duct.
– Check that the sealing strip, the insert
and the cone are undamaged.
– Check that no objects prevent the cone
of textile from closing/opening.
Maintenance EKO-BSV1, 2, 4
och 5
External and internal control
When cleaning or at least every three years,
check the protective cover and insert. Also
check that the corrosion protection is intact.
– Check the outer casing of the cover so
that it is not damaged.
– Open the 2 locking latches (BSV1 and
4) or remove the hatch (BSV2 and 5)
and then remove the insert.
– Check that the Sealings, the insert and
the cone are undamaged.
– Check that no objects prevent the cone
of textile from closing/opening.
– Clean if necessary.
– Put back the insert and lock the two
locking latches (BSV1 and 4) or put
back the hatch (BSV2 and 5).
Note! After checking and cleaning, the
insert must be mounted so that the ar-
row points in the air direction and that
the stop pin (3) or the locking device (4,
5) is according to pictures.
– Clean if necessary.
– Reassemble the insert in the spiro duct
and screw back the star handle (2).