EKOVENT AB 

We reserve the right to make changes 

2020-12

Type approval SC0800-14.

Assembly instruction EKO- BSV1, 2, 4 och 5 

1.  Self-actuating backflow protector EKO-

BSV can be mounted in a vertical or 
horizontal duct, in or outside a fire cell. 
Protection against the spread of fire 
between fire cells by transferring heat 
via the ventilation ducts is not reduced 
with this backflow protection, which is 
why special measures must be taken 
to solve this.

Installation of EKO-BSV1, 2, 4 och 5

Textile cone, position at 3 m/s

EKO-BSV Textilkon Dim_100-125

EKO-BSV Textilkon Dim_160-200

Diameter 100-125 mm

Diameter 160-200 mm

Distribution duct

Possibly Iris damper

Air direction

EKO-BSV

Fire seal

Fire insulation

Fire cell boundary

2.   It is important to ensure that the Self-

actuating backflow protector is moun-
ted in the correct air direction accor-
ding to the arrow on the protector.

3. 

NOTE!

 When adjusting, the system 

must be in operation.

Summary of Contents for EKO-BSV Series

Page 1: ...Installation operating and maintenance instructions 2020 12 Self actuating backflow protector EKO BSV ...

Page 2: ... of manufacture EKOVENT AB Vellinge Certification Product type description Type approval number RISE Certification 1002 EKO BSV SC0800 14 Installation operating and maintenance instructions EKO BSV Product handling 3 General assembly 4 Installation instructions 5 Operation and maintenance 6 ...

Page 3: ...ontact the supplier immediately Storage The storage of materials on the site should be planned so that you get the least pos sible internal transport Self actuating backflow protectors must be protected against water and always stored in a dry place Furthermore they must be handled so that no mechanical damage occurs to them Commissioning The Self actuating backflow protectors must not be put into...

Page 4: ...Mounting can be done horizontally or vertically in a fire cell in a shaft or in a cor ridor in such a way that it can be inspected and cleaned The fire properties are tested according to the same test standard as for CE marked Fire Damper Fire properties corresponding to E90 applies provided that EKO BSV is mounted in a duct outside the fire exposed fire cell applies to both wall and floor When EK...

Page 5: ...h this backflow protection which is why special measures must be taken to solve this Installation of EKO BSV1 2 4 och 5 Textile cone position at 3 m s EKO BSV Textilkon Dim_100 125 EKO BSV Textilkon Dim_160 200 Diameter 100 125 mm Diameter 160 200 mm Distribution duct Possibly Iris damper Air direction EKO BSV Fire seal Fire insulation Fire cell boundary 2 It is important to ensure that the Self a...

Page 6: ...nt EKO BSV Insert in each spiro duct Attach the mounting bracket to the adja cent building part with a suitable dressing Operation Self actuating backflow protector EKO BSV is a type approved protection intended as protection against the spread of smoke in ventilation systems of the fan type in operation EKO BSV closes when a fire occurs in a room and the pressure rises The product is self acting ...

Page 7: ...ck the protective cover and insert Also check that the corrosion protection is intact Check the outer casing of the cover so that it is not damaged Open the 2 locking latches BSV1 and 4 or remove the hatch BSV2 and 5 and then remove the insert Check that the Sealings the insert and the cone are undamaged Check that no objects prevent the cone of textile from closing opening Clean if necessary Put ...

Page 8: ...jselgatan 7 235 32 Vellinge Tel 040 42 16 00 www ekovent se info ekovent se REGIONAL OFFICE GÖTEBORG Boråsvägen 5 435 31 Mölnlycke Tel 031 23 07 40 REGIONAL OFFICE STOCKHOLM Vallgatan 9 170 67 Solna Tel 08 508 613 00 ...

Reviews: