Fuel Quantity and Pellets Travel Time to Burner

 

 
The  time  pellets  take  from  store  to  burner,  depends  on  the  pellets  storage  location  in  relationship  to  the  burners 
location.  There  are  several  models  of  screw-feed  to  chose  from,  each  model  can  be  configured  and  rigged 
differently to convey pellets to the burner.  
To  avoid  uneven  pellets  delivery  to  the  burner  and  varying  priming-measure  quantities  feeding  the  burner,  the 
screw-feed should not be at more than a 45

angel to the horizontal floor plane.  

Provide an intermediate storage to ensure continuous and even delivery. Delivery times of pellets from storage to 
the burner will be afected by the size and condition of the pellets and the angle of the feed-screw to the horizontal 
plane. 
Test  the  delivery  time  of  the  pellets  through  the  feed-screw  to  the  boiler.  Allow  the  feed-screw  to  operate  at  full 
speed for 3 minutes. Collect the pellets discharged from the feed-screw, weigh the pellets. By checking this weight 
against  the  table  below,  it  is  possible  to  establish  the  kW  effect  output  and  boiler  efficiency  obtained  from  the 
amount of pellets delivered.    
 
 

Boiler Efficiency Table  (1kg pellets = 4.8kWh) 

 

Actual Energy Supply 

Pellets in gram weight 

per 3 minutes / kg per 

hour 

Approx. volume Pellets in 

decilitres per 3 min. 

Indicated effect at 80% 

boiler efficiency 

500 kW 

5 210 / 104,15 

80 

400 kW 

700 kW 

7 294 / 145,81 

112 

560 kW 

 

 
 
 
Adjustment of Air Supply To Burner (operating without activated lambda sond). 

 
On  initial  installation  of  burner  and  subsequent  adjustment  of flame, check the colour of the flame. For maximum 
efficiency, the flame should be light orange in colour. A white flame indicates too much air supply. A dark, red flame 
indicates  too  little  air  supply.  Adjust  the  speed  of  the  bith  fans  using  the  burner’s  digital  control  system.  After 
changing any settings allow the burner to operate for 2-3 minutes before carrying out a further test. This allows the 
change of setting to be activated and run-in. 
If changing the quality of pellets, adjusting the settings of the burner may be required to maintain efficient burning.  
The above is an initial and approximated setting. For finer adjustment, a flue-gas measuring device will be required. 
NOTE:  When  burning  pellets,  settings  and  the  appearance  of  the  flame  will  continuously  show  very  minor 
variations – this is normal and not an indication of a fault. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for eurofire XL-GRYM

Page 1: ...Datum 080708 rev 0 eurofire XL GRYM 500 700 kW The Pellet Burner of the 21 st Century Ekosystem AB Bj rkev gen 84 S 805 97 G VLE Sweden...

Page 2: ...Chamber 8 Photocell 8 Setting the Thermostats 8 Pellets Priming Measure 8 Start and Stopp the Burner 8 Fuel Quantity and Pellets Travel Time to the Burner 9 Adjustment of Air Supply to the Burner 9 Ma...

Page 3: ...n This guarantee does not cover direct or indirect injuries to third parties or damage to property Cost of labour for replacement of components is not included in the guarantee Ekosystem AB will excha...

Page 4: ...r than 45 Fill up with pellets enough to cover the feed screw inlet properly Connect the screw to a power point and run it until it is completely filled with pellets Design and internal structure The...

Page 5: ...ney draught of 15 30 Pa is sufficient to run the burner at optimum If the internal area of the chimney is too large to allow 15 30 Pa a draught stabilizer can be installed to decrease the flue area If...

Page 6: ...6 Construction of the burner Hood Secondary Air Supply Internal Feed Screw Burner Cassette Primary Air Supply Igniters...

Page 7: ...trol Cabel Internal Feed Screw Motor Sprinkler Feed Tube Clamp Sprinkler s termosensor Secondary Air Supply Fan Internal Feed Screw Electric Box Primary Air Supply Fan Service Inlet Overheating termos...

Page 8: ...s own internal temperature gauge and regulator that controls and adjusts the burner It can be operated by setting the wanted output temperature within which the burner will operate see TM3007 User Man...

Page 9: ...from the amount of pellets delivered Boiler Efficiency Table 1kg pellets 4 8kWh Actual Energy Supply Pellets in gram weight per 3 minutes kg per hour Approx volume Pellets in decilitres per 3 min Ind...

Page 10: ...protection system is placed on the fall tube In the event of the alarm being triggered always investigate the cause and rectify Cause for an alarm may be a closed damper blocked convection tube not en...

Page 11: ...burner this reduces the number of start ups and saves fuel The regulator s gauge displays the current boiler temperature in the display panel of the boiler s MPU Controll Unit Ensure the immersion te...

Page 12: ...Pellets recomendation Diameter mm 6 8 Max length mm 32 The eurofire pellets burner including its control unit and feed screw system is CE certified and is manufactured and documented to the following...

Page 13: ...13 Drowing Dimensions...

Page 14: ...tailer Company Name Consultant Name Address Postal code Contact person Telephone Cell Fax E mail Type Output Manufacturers number Date of Manufacturer Measured and Installed Settings Date CO ppm CO2 F...

Reviews: