4
EKOSync 1588 User Manual rev 3.10
EKOSync 1588 PTP TIME SERVER
I. FEATURES & SPECIFICATIONS
1
Description
EKOSync 1588 PTP Time Server provides sub-microsecond accuracy time information for
synchronizing energy distribution subsystem intelligent electronic devices, and proceeding
according to IEEE 1588 v2 time protocol. Product includes adjustable hold-over times for
discontinuities with GPS communication, and compensation for antenna reception distortions.
2
Features
DC IRIG-B (Unmodulated, DCLS - C37.118, not ready in this version)
TCP/IP remote M&C management option
Synchronized TOD (Time of Day) and PPS (Pulse per second) outputs
User defined 10MHz/5MHz frequency output
TCP/IP configuration option
NTP/ SNTP (IEC 61850)
SNMP v1, v2c & v3
IEEE 1588 PTP Server
18-75V DC Isolated power supply
Password protection and user authentication
3
Specifications
Electrical:
Input
Power Supply
Voltage:
18 to 75 V DC
Power consumption: 10W max
Ethernet (RJ45 UTP)
10/100Mbps
Isolation
Power to GPS input
3 kV
Power to I/O
3 kV
Outputs
Relay output
250V 150mA
4 TTL outputs
Time codes or pulses or user defined