Ved alarm se under fejlfinding.
Menu / Fitter settings/
Designation
Area
Standard
Description
Ignition fuel
0 – 200g.
150 – 200g.
How many grams are taken in before starting up. This
depends on the type of boiler.
If the boiler uses more than 3 – 4 minutes on starting up,
the amount can be reduced/increased by 10 gram per time,
until the ideal time of ignition has been reached.
Travel of the bottom plate
0 – 100 sek.
40
This is how many seconds the ash plate moves each way
to push out the ash. If it has not activated the micro
switch within a preset number of seconds, the boiler
goes in alert.
Do never activate the micro switch manually as this will destroy the thread for the spindle.
Efficiency for flue suction
0 – 100 %
100 %
Here you can adjust how much air need to be added in
proportion to efficiency in percent. You can adjust per 10
%. These numbers have been preset and it is
recommended
not
to adjust these. We recommend to use
the section ”General” to increase / reduce the amount of
air. If you reduce the amount to 95 %, then all groups are
reduced by 5 % and if you write 105 %, the amount of air
is increased by 5 % in general. Notice that changes under
general, cannot be seen on the front page of the display.
Percentage must always be rising.
Optional equipment
Optional equipment is activated here, e.g. flue gas
temperature sensor or the VVB priority sensor. This is
done by pressing ”No”, so it changes to ”Yes”. Please
note that there are 2 pages with optional equipment and
to go to page 2, press ”Next
”.