Page 4
The controller
Start:
When you press this button, the boiler
starts and the text changes to ”Stop”.
Stop:
When you press this button, the boiler
stops and the text changes to ”Start”.
Info:
Here you find information concerning the
boiler.
Operation time in hours.
Number of ignitions
(reset by changing electrical igniter).
Software version.
Controller id.
Boiler type.
Menu / User settings/
Designation
Area
Standard
Description
Boiler temperature
40˚ – 80˚
60˚
Here you set the wanted boiler temperature.
Should not be below 60° and always 10° higher than the set point of
the shunt valve.
Fuel
0 > *
Kilogram pellets, which are added per hour, at 100 %
combustion. Ekoheat type 900 = 2,2 Ekoheat type 2500 =
5,6
Ekoheat type 1500 = 3,1 Ekoheat type 4000 = 8,8.
Menu / User settings/Cleaning/Adjust/
Fan interval
0 - 120
45
Minutes between air cleaning of flue gas ducts in the boiler.
Time for air cleaning
10 - 30
10
Seconds the flue suction runs during air cleaning of flue gas
ducts per time.
Ash plate
0>
**
Number of kilogram pellets, which the boiler takes in, between
cleanings.