Troubleshooting
AIM2505A Technical Manual V2.03
36
3. Choose 2 for CIAO to get to the ciao_tc main menu (TC MENU)
Make a selection:2<EMTER>
- /dev/iobus ------------------------------------------------------------
* 0 ** TC MENU
1 01 DIO DIO2378A 112415 1 H 38
112626
2 02 DIO DIO2378A 112422 1 H 0
112668
3 06 AIM AIM2505A 123123 0 H 0
103291
The list shows all I/O modules on the I/O bus, each on their own row. The
modules from 1-9 are indicated by decimal numbers. If there are more than
nine, modules starting from 10 are indicated by a letter a-z. In the above
example, there are two DIO modules and one AIM module on the I/O bus.
A row starting with
3
contains the following information:
3
= Remote Terminal number, [range from 1 to 9 and a to z]
06
= node number
AIM2505A
= Module name
123123
= Module serial number
0 H 0 103291
= Additional module information
4. Select the module by typing the number (or letter) at the
TC MENU
.
This starts the Remote Terminal connection. Once the connection has been
established,
ciao_tc
prints the information about the selected module (the
same that was seen at the
TC MENU
module list) and shows that the AIM
Remote Terminal has started:
-------- 1 01 AIM - AIM2505A 123123 0 ------------------------------------
AIM2505A start
RST=00
B015.P0000.001-0.01 AIM2505A 41 C
FPGAID: A2590-AIM-pp-26
>
The AIM Remote Terminal is now ready to accept commands:
Pressing
CTRL+A
followed by 0 will return to the
ciao_tc
main menu
(
TC MENU
), where a new module can be selected.
Pressing
CTRL+C
at any time exits the
ciao_tc
and control returns to CPU
console.
Pressing
E
NTER
prints the
ciao_tc
command prompt
>
.