background image

 

 

 

 

Page 10 of 16 

Drawing   : - TPC470 
Issue 

: - 1 

Date 

: - 09/02/17 

 
 

RM40 

SPARE PARTS LIST 

    

    

    

N

UMBER

 

D

ESCRIPTION

 

P

ART 

N

UMBER

 

Q

UANTITY

 

Timer 

1617990 

Condenser coil 

2131147 

Evaporator coil 

1018611 

Drain tray 

2018705 

Filter 

1019712 

Capillary 

3014250 

1.64ft 

Solenoid valve 

3020836 

Filter dryer 

3020937 

Solenoid coil 

3030451 

10 

On/Off switch 

3035914 

11 

Fan Motor 

3035773 

12 

Fan Blade 

3040181 

13 

Castor 

3050205 

14 

Compressor 

3022147 

15 

Water Container Assy 

1137907 

16 

Bucket Micro Switch 

3033033 

17 

Humidistat Knob 

2018644 

18 

Bucket Full Lens 

3032271 

19 

Bucket Full Light 

3036636 

20 

Humidistat 

3035158 

21 

Mains Cable 

2141095 

22 

Front Grille 

2018704 

Summary of Contents for 10187MG-US

Page 1: ...Page 1 of 16 Drawing TPC470 Issue 1 Date 09 02 17 RM40 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk ...

Page 2: ...e 2 of 16 Drawing TPC470 Issue 1 Date 09 02 17 RM40 PACKAGE CONTENTS Item Description Quantity 10187MG US Dehumidifier 1 3086144 Quick release hose coupling 1 3944110 PVC Tube 3 8 I D 7 8M TPC470 Manual 1 ...

Page 3: ...ng the same energy removed during the cooling phase plus the additional heat generated by the compressor The air is therefore discharged from the dehumidifier at a slightly higher temperature with a lower absolute humidity than that which entered Continuous circulation of air through the dehumidifier gradually reduces the relative humidity within the area The RM40 dehumidifier is a rugged reliable...

Page 4: ...erants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data label MODEL 10187MG US HEIGHT 24 2 615 mm WIDTH 15 382 mm DEPTH 14 4 365 mm WEIGHT 57lbs 26 kg AIRFLOW 88 3CFM 150 M3 Hr POWER SUPPLY 110V 60Hz 1 ph FINISH Rotational Moulded polyethylene OPERATING RANGE ...

Page 5: ...ible that the humidistat setting is too low and may need increasing Conversely if you no longer have condensation and the unit is still operating then the humidistat setting may need reducing EMPTYING THE WATER CONTAINER When the water container is full an internal float mechanism will switch the unit off This is indicated by the illumination of the full light on the front control panel The water ...

Page 6: ... temperature is below 25 C an even coating of frost should cover the entire evaporator coil If the air temperature is above 25 C frost and or droplets of condensed water should cover the entire evaporator coil 6 When the unit is operated in ambient of less than 15 C a defrost cycle should occur approximately every hour The exact time is impossible to predict as the unit is fitted with a temperatur...

Page 7: ...ing accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all wiring connections including mains cable for damage or loose connections 5 In order to check the defrost operation the unit needs to be operated in an ambient temperature of less than 15 C for at least 1 hour When operated In this condition the unit should defrost at least once every...

Page 8: ...the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing further loss of refrigerant gas 3 The refrigerant compressor fitted to the dehumidifier is a durable unit that should give many years of service Compressor failure can result from the machine losing ...

Page 9: ... fault 3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass valve 1 Contact the Factory Service Center 2 Contact the Factory Service Center Unit vibrates excessively 1 Loose compressor 2 Damaged fan 1 Tighten the nuts on the compressor mounts 2 Replace fan Wate...

Page 10: ...3014250 1 64ft 7 Solenoid valve 3020836 1 8 Filter dryer 3020937 1 9 Solenoid coil 3030451 1 10 On Off switch 3035914 1 11 Fan Motor 3035773 1 12 Fan Blade 3040181 1 13 Castor 3050205 4 14 Compressor 3022147 1 15 Water Container Assy 1137907 1 16 Bucket Micro Switch 3033033 1 17 Humidistat Knob 2018644 1 18 Bucket Full Lens 3032271 1 19 Bucket Full Light 3036636 1 20 Humidistat 3035158 1 21 Mains ...

Page 11: ...yoto Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data label Due to the high pressures within the refrigeration circuit under no circumstances must direct ...

Page 12: ... WRITTEN OR IMPLIED WARRANTY WITH RESPECT TO THE FOREGOING DESCRIBED MERCHANDISE For Your Records Model ____________________ S N ______________________ Date Received ______________ SAVE THIS SECTION FOR YOUR RECORDS CLIP AND RETURN THIS CARD PLEASE NOTE WARRANTY REGISTRATION To ensure that your Ebac Dehumidifier is accorded the full coverage provided by this warranty please complete and mail this ...

Page 13: ...Page 13 of 16 Drawing TPC470 Issue 1 Date 09 02 17 ...

Page 14: ...Page 14 of 16 Drawing TPC470 Issue 1 Date 09 02 17 ...

Page 15: ...Page 15 of 16 Drawing TPC470 Issue 1 Date 09 02 17 ...

Page 16: ...www eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www ebacusa com sales ebacusa com German Sales Office Ebac Industrial Products Ltd Gartenfelder Str 29 37 Gebäude 35 D 13599 Berlin Germany Tel 49 3043 557241 Fax 49 3043 557240 www eip ltd de sales eip ltd...

Reviews: