Drawing   : TPC465 
Issue 

: C 

Date 

: 05/01/2017 

 

 

 

Control Settings 

 
Once  the  unit  is  positioned  correctly,  required  duct  work  attached  and  the 
power supply connected, the process fan speed and temperature control need 
to be set correctly. 
 
The  fan  speed  control  is  located  within  the  main  electrical  control.  The 
controls are numbered 1 to 10, with 10 being the maximum speed.  
 
For normal (efficient) operation the process airflow should be set to 3000m³/h 
(1766  cfm).  Measurements  should  be  taken  at  the  duct  outlets  using  a 
suitable instrument. 
 
The  regeneration  air  flow  is  fixed  and  cannot  be  adjusted.  Setting  of  the 
correct  airflow    is  to  be  carried  out  by  the  installation  of  a  damper  control 
within the regeneration outlet airstream, 
 
The temperature control regulates the temperature of the reactivation airflow 
onto the desiccant wheel. The control can be set up to a maximum of 145°C 
The controller displays the set value (Green display) and also the actual value 
(Red display) 
To adjust the temperature control simply press the 

 or 

 buttons to select 

the required setting. The controller will automatically store this value.  
 
The  temperature  setting  should  be  set  to  90°C  above  the  ambient 
temperature of the area being dehumidified 
 
If  high  moisture  extraction  is  required  it  will  be  necessary  to  increase  the 
process airflow. The temperature control setting should also be increased. 
 
If  very  low  humidity  levels  are  required  then  the  process  airflow  should  be 
reduced. 
 
The following table should be used as a guide: 
 
 

 

PROCESS AIR 

FLOW 

(M³/H)

 

REGEN AIR 

FLOW 

(M³/H)

 

TEMPERATURE 

RISE 

(K)

 

STANDARD 

(EFFICIENT) 

3000 

750 

90 

HIGH 

EXTRACTION 

3500 

750 

110 

DEEP DRYING 

(LOW RH) 

2500 

750 

110 

 
 

Summary of Contents for DD3000

Page 1: ...Drawing TPC465 Issue C Date 05 01 2017 DD3000 460V 3PH 60HZ INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Page 2: ...e moisture content of the rotor is increased A smaller volume of air the reactivation air is heated by an internal heater and passes through a portion of the rotor in the opposite direction As this he...

Page 3: ...OUTLET DIAMETER 400mm 15 75 REGENERATION AIR OUTLET DIAMETER 250mm 9 84 ROTOR WHEEL SPEED 13 6 RPH ROTOR SIZE DIA X DEPTH 650mm 25 6 x 200mm 7 9 HIGH EXTRACTION SETTING 27 C 60 RH 568 l day 1200 ppd...

Page 4: ...conditions of the area to be dehumidified will determine the amount of water extraction the unit is cable of Measure the ambient conditions of the area to be determined and then use that information w...

Page 5: ...spigot is 16 diameter and only 168 ducting or greater should be attached Both the regeneration and process air inlets are provided with filters The dimensions of the ducts are as follows Process air...

Page 6: ...mperature control regulates the temperature of the reactivation airflow onto the desiccant wheel The control can be set up to a maximum of 145 C The controller displays the set value Green display and...

Page 7: ...ue C Date 05 01 2017 FAN PERFORMANCE CURVES For example If the total system resistance is 600pa then the process fan selector would have to be set to No 5 to achieve the required airflow of 3000m h 17...

Page 8: ...motor PROCESS FAN FAULT lamp RED Fault on the process motor HIGH TEMPERATURE FAULT lamp RED Overheat protection within the heater duct has operated To start the dehumidifier switch the ISOLATOR to th...

Page 9: ...perate switching off the heaters The fans and drive motor will continue to operate but the HIGH TEMPERATURE fault lamp will illuminate Prior to resetting the protector check that the dehumidifier is i...

Page 10: ...ILLES ON THE MACHINE DO NOT COVER OR OBSTRUCT AIRFLOW FROM THE GRILLES DO NOT OPERATE THE UNIT WITH THE COVERS REMOVED DO NOT ATTEMPT ANY REPAIRS SHOULD THE UNIT FAIL TO OPERATE DO NOT STAND ON THE UN...

Page 11: ...Manual The rotor is maintenance free However should it be necessary to clean the rotor compressed air should be used to carefully blow dirt from the rotor The heaters are maintenance free However sho...

Page 12: ...ced airflow Check fans duct No rotation of Rotor Check belt tension drive motor Air leakage Check sealing Dehumidifier does not start No power Check fuse Correct switch setting Check Auto Manual switc...

Page 13: ...Drawing TPC465 Issue C Date 05 01 2017...

Page 14: ...physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the application in a safe way and understand the hazar...

Page 15: ......

Page 16: ......

Page 17: ...l co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www ebacusa c...

Reviews: