background image

 

 

 

 

Drawing   : TPC465 
Issue 

: C 

Date 

: 05/01/2017 

 

 

INSTALLATION 

 

The DD3000 is designed for indoor use. The unit should be placed on a level 
surface and a space of 1 meter free around all faces to allow access for any 
duct work and servicing. 
 
 

Connecting duct work: 

 
The  regeneration  outlet  must  be  ducted  to  outside  the  area  being 
dehumidified.  The  outlet  duct  spigot  is  10”  diameter  and  only  10”  ducting  or 
greater  should  be  attached.  A  damper  for  adjusting  the  airflow  must  be 
installed 
 
The  process  outlet  can  be  ducted  to  a  specific  area  or  another  room.  The 
outlet duct spigot is 16” diameter and only 168” ducting or greater should be 
attached. 
 
Both  the  regeneration  and  process  air  inlets  are  provided  with  filters.  The 
dimensions of the ducts are as follows: 

Process air inlet L 740mm x W 535mm (29.1” x 21”) 
Regeneration air inlet L 485mm x W 485mm (19.1” x 19.1”0 
 

Power Supply & Humidistat Control: 

 
The unit must be connected to a suitable 460V, 3 phase, 50Hz supply. 
 
 
 
 
 
 
Feed  power  cables  through  the  gland  provided  and  then  wire  the  unit  as 
shown below. 
 
An external humidistat can also be used to control the relative humidity in the 
dehumidified area. If a humidistat is used then the wires should pass through 
the gland provided and then wired as shown in the diagram at the back of this 
manual. 
 
 
 

-WARNING

-  

THIS APPLIANCE MUST BE EARTHED

 

Summary of Contents for DD3000

Page 1: ...Drawing TPC465 Issue C Date 05 01 2017 DD3000 460V 3PH 60HZ INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Page 2: ...e moisture content of the rotor is increased A smaller volume of air the reactivation air is heated by an internal heater and passes through a portion of the rotor in the opposite direction As this he...

Page 3: ...OUTLET DIAMETER 400mm 15 75 REGENERATION AIR OUTLET DIAMETER 250mm 9 84 ROTOR WHEEL SPEED 13 6 RPH ROTOR SIZE DIA X DEPTH 650mm 25 6 x 200mm 7 9 HIGH EXTRACTION SETTING 27 C 60 RH 568 l day 1200 ppd...

Page 4: ...conditions of the area to be dehumidified will determine the amount of water extraction the unit is cable of Measure the ambient conditions of the area to be determined and then use that information w...

Page 5: ...spigot is 16 diameter and only 168 ducting or greater should be attached Both the regeneration and process air inlets are provided with filters The dimensions of the ducts are as follows Process air...

Page 6: ...mperature control regulates the temperature of the reactivation airflow onto the desiccant wheel The control can be set up to a maximum of 145 C The controller displays the set value Green display and...

Page 7: ...ue C Date 05 01 2017 FAN PERFORMANCE CURVES For example If the total system resistance is 600pa then the process fan selector would have to be set to No 5 to achieve the required airflow of 3000m h 17...

Page 8: ...motor PROCESS FAN FAULT lamp RED Fault on the process motor HIGH TEMPERATURE FAULT lamp RED Overheat protection within the heater duct has operated To start the dehumidifier switch the ISOLATOR to th...

Page 9: ...perate switching off the heaters The fans and drive motor will continue to operate but the HIGH TEMPERATURE fault lamp will illuminate Prior to resetting the protector check that the dehumidifier is i...

Page 10: ...ILLES ON THE MACHINE DO NOT COVER OR OBSTRUCT AIRFLOW FROM THE GRILLES DO NOT OPERATE THE UNIT WITH THE COVERS REMOVED DO NOT ATTEMPT ANY REPAIRS SHOULD THE UNIT FAIL TO OPERATE DO NOT STAND ON THE UN...

Page 11: ...Manual The rotor is maintenance free However should it be necessary to clean the rotor compressed air should be used to carefully blow dirt from the rotor The heaters are maintenance free However sho...

Page 12: ...ced airflow Check fans duct No rotation of Rotor Check belt tension drive motor Air leakage Check sealing Dehumidifier does not start No power Check fuse Correct switch setting Check Auto Manual switc...

Page 13: ...Drawing TPC465 Issue C Date 05 01 2017...

Page 14: ...physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the application in a safe way and understand the hazar...

Page 15: ......

Page 16: ......

Page 17: ...l co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www ebacusa c...

Reviews: