Drawing   : - TPC433 
Issue 

: - 2 

Date 

: - 24/11/16 

 

OPERATION 

 

The  following  procedures  should  be  followed  to  test  the  RM85H  for  correct 
operation: 
 

 

1. 

After  unpacking,  examine  all  external  features  to  confirm  damage-
free shipment. Report all defects and damage at once.  Connect the 
power  cable  to  a  grounded  15  Amp  electrical  outlet.  Connect  the 
drainage  outlet  to  a  suitably  sized  hose  and  run  the  hose  to  a 
permanent drain 

 

2.     Setting the Digital Humidistat 

The  Digital  Humidistat  is  factory  preset  to  give  the  optimum 
level  of  control.  Only  adjustment  of  the  desired  set  point  is 
required. 

 
During normal operation, the display shows  the current % Relative 
Humidity within the space being conditioned.  
 
The required humidity level can be set as follows: 

 

Press the “S” button once to access the set point 

 

Press  the 

  or 

  button  to  change  the  display  to  the  

desired Humidity level 

 

Press  the  “S”  button  again  to  save  the  set  point  –  The 

control  returns  to  displaying  the  current  %  Relative 
Humidity  

 

 

3. 

Check dehumidification process as follows: 

 

 
 

 

A. 

Place unit on a level surface. 

 

 

B. 

Start up unit by switching to “I”. 

C.    Ensure the Humidity Control is set to 40% 

 

 

C.   Check that the compressor is running. 

 

 

D. 

Leave the machine running for 15 minutes. 

 

 

E.   Observe the evaporator coils through the front grille, to confirm 

frost formation. 

   

 

(i) If the air temperature is below 78

°

F, an even coating of frost 

should cover the entire evaporator coil.   

   

 

(ii) If the air temperature is above 78

°

F, frost and/or droplets of 

condensed water should cover the entire evaporator coil. 

 
 

CAUTION: 

DO NOT REMOVE COVERS WHEN UNIT IS IN OPERATION 

Summary of Contents for 10560RH-US

Page 1: ...Page 1 of 12 Drawing TPC433 Issue 2 Date 24 11 16 RM85H INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Page 2: ...2 of 12 Drawing TPC433 Issue 2 Date 24 11 16 RM85H PACKAGE CONTENTS Item Description Quantity 10560RH US Dehumidifier 1 3086144 Quick release hose coupling 1 3944110 PVC Tube 3 8 I D 7 8M TPC433 Manu...

Page 3: ...e cooled air then passes through the hot condenser coil where it is reheated using the same energy removed during the cooling phase plus the additional heat generated by the compressor The air is ther...

Page 4: ...erants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data labe...

Page 5: ...ned The required humidity level can be set as follows Press the S button once to access the set point Press the or button to change the display to the desired Humidity level Press the S button again t...

Page 6: ...t melting This is quite normal and the display will return to its normal reading when the unit returns to dehumidifying mode Fan running If after carrying out the above procedures the unit does not ap...

Page 7: ...r than frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all wiring connections 5 In order to check the defrost operati...

Page 8: ...he refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing...

Page 9: ...fault 3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass va...

Page 10: ...6 Filter 2056004 1 7 Capillary 3014254 2 X 2ft 8 Solenoid valve 3020837 1 9 Filter dryer 3020909 1 10 Compressor 3022198 1 11 Defrost Relay 3030269 1 12 Solenoid coil 3030451 1 13 Humidity Controller...

Page 11: ...oto Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R40...

Page 12: ...ww eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www eba...

Reviews: