When  the  unit  is  operated  in  ambient  of  less  than  59°F,  a 
defrost  cycle  should  occur  approximately  every  ½  hour.  The 
exact  time  is  impossible  to  predict  as  the  unit  is  fitted  with  a 
temperature sensitive defrost control. During this defrost cycle 
the fan will switch off. 

 

When  the  unit  is  defrosting,  the  %  Relative  Humidity  displayed  on  the 
digital controller may increase as a result of the ice / frost melting. This 
is quite normal and the display will return to its normal reading when the 
unit returns to dehumidifying mode. (Fan running) 
 
 
  

If, after carrying out the above procedures, the unit does not appear to 

function properly, refer to the 

Trouble Shooting

 section, which follows, 

or contact the Factory Service Center. 

 
 
 
 
 
 
 
After using the RM85H, turn it off for five minutes to allow the condensate on 
the coils to drain into the pump reservoir, then press the momentary pump 
purge switch for twenty to thirty seconds to evacuate the water from the pump 
reservoir. 

CAUTION: 

ONCE THE UNIT HAS BEEN SWITCHED OFF, WAIT AT 

LEAST FIVE MINUTES BEFORE RESTARTING. 

Summary of Contents for 10560RH-US

Page 1: ...Page 1 of 12 Drawing TPC433 Issue 2 Date 24 11 16 RM85H INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Page 2: ...2 of 12 Drawing TPC433 Issue 2 Date 24 11 16 RM85H PACKAGE CONTENTS Item Description Quantity 10560RH US Dehumidifier 1 3086144 Quick release hose coupling 1 3944110 PVC Tube 3 8 I D 7 8M TPC433 Manu...

Page 3: ...e cooled air then passes through the hot condenser coil where it is reheated using the same energy removed during the cooling phase plus the additional heat generated by the compressor The air is ther...

Page 4: ...erants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data labe...

Page 5: ...ned The required humidity level can be set as follows Press the S button once to access the set point Press the or button to change the display to the desired Humidity level Press the S button again t...

Page 6: ...t melting This is quite normal and the display will return to its normal reading when the unit returns to dehumidifying mode Fan running If after carrying out the above procedures the unit does not ap...

Page 7: ...r than frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all wiring connections 5 In order to check the defrost operati...

Page 8: ...he refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing...

Page 9: ...fault 3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass va...

Page 10: ...6 Filter 2056004 1 7 Capillary 3014254 2 X 2ft 8 Solenoid valve 3020837 1 9 Filter dryer 3020909 1 10 Compressor 3022198 1 11 Defrost Relay 3030269 1 12 Solenoid coil 3030451 1 13 Humidity Controller...

Page 11: ...oto Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R40...

Page 12: ...ww eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www eba...

Reviews: