EHV GmbH • Entwicklung | Herstellung | Vertrieb • Hauptstraße 131 • 01744 Dippoldiswalde
6
1.5. Couplers
The coupler between the heat system and the exhaust system (chimney) ought
to be as short as possible, straight and needs to be installed in rising position.
You may need to caulk the links. For cleaning the couplers, there ought to be at
least one opening left free. The material density must not fall below 2 mm.
1.6. Fire protection – distance to combustible components and furniture
forward
from the side
with side plate /
without side plate
back
Kanuk® 3 Classic
80 cm
50 cm / 80 cm
40 cm
Kanuk® 4 Classic
80 cm
55 cm / 90 cm
40 cm
Kanuk® 3 with hotplate
80 cm
50 cm / 80 cm
40 cm
Kanuk® 4 with hotplate
80 cm
55 cm / 90 cm
40 cm
forward
from the side
back
Kanuk® Turbo 1
80 cm
80 cm
40 cm
Kanuk® Turbo 2
80 cm
90 cm
40 cm
CONSTRUCTION MANUAL
Flammable floor coverings
have to be protected by fire-
resistant material.
In addition the material needs
to be placed also at least 50
cm in front of the stove and
30 cm next to it.
1.7. Chimneys
Kanuk® hot-air kilns don’t require a chimney of their own if the door
spring was fitted for layout 1. The combustion measurements were
carried out according to the norm DIN 13384 parts 1, 2 and 3 with the value
triplet given in table 1.