RCL-CXXW_EHC_Rev.0_05-12-2018
7
/
26
Fig1
Minimum Clearances
Note:
Only IPX4 heaters are suitable for installation in bathrooms which allows
for the heater to be installed within Zone 2 as per regulation 701.32.4
Regulation 701.411.3.3 of BS7671 means that all circuits within a location
containing a bath or shower will require RCD protection not exceeding 30 mA
and have the characteristics specified in regulation 415.1.
Local isolation should be provided for the heater, however, the isolation device
must be installed out with all zones and in compliance with regulation
701.512.3 and Section 53 of BS7671
Note:
Heaters must be only installed in or out with zone 2 of a bathroom
Possible Shelf