14
5.5.3 PCS to BMS communication cable
This cable is specific to the battery model. Refer to the instruction that applies only to the battery module suppled.
1.
Terminate the PCS-BMS cable in battery #1 as shown in figure 11. This battery is herein referred to as the “Master” battery
module. All other modules sync to the master.
Model US3000: Terminate the PCS - BMS jumper cable in the [CAN] port of battery #1.
Model US3000C: Terminate the PCS – BMS / Console Y cable jumper in the [A/CAN] and [Console] ports of battery #1.
2.
Route the other end of the cable through the PCS port hole and terminate in the cable in the [BMS OUT] port as shown in
figure 11.
3.
Terminate the two BMS jumper cables referenced C1 between batteries #1-2 and #3-4.
BMS OUT
1
US3000C
US3000
#3810
#3787
Figure 11: PCS to BMS communication cable connection.