2.2 Installation conduit plan – power and communication circuits
The following example outlines the conduit plan for power and communication circuits for a complete solar plus storage
system using the Evolve Hub and the Evolve ESS. (String PV inverter shown – replace with equivalent AC combined micro-
inverter output, where applicable).
Table 1: Circuit summary for a solar plus storage installation.
Evolve Hub 40 Amp
Conduit
Ref
Circuit Definition
Conductor
(recommended)
Circuit Protection
P1
ESS grid power
8/3
40 Amp
P2
ESS backup power
8/3
40 Amp
P3
Main panel power
8/3
40 Amp
P4
Backup panel
8/3
40 Amp feeder if total backup ccts exceed 40 Amp/240V
rating
P5
Solar PV power
8/3
40 Amp
S1
EMS communication cable
3 meter patch cable included
CAT 5/6 STP
-
S2 (x2)
CT , 50 Amp 8 ft pigtail
18/2, 300V
-1
-
S3
AK1 Hub Control Signal cable
harness included , 10 ft
18/2, 300V
-
S4 (x2)
CT, 200 Amp 8ft pigtail
18/2, 300V
-1
-
S5
CT , 50 Amp 8 ft pigtail
18/2, 300V
-1
-
Note 1: Conductor type referenced where Hub is installed greater than 24” from the Evolve ESS. Signal wiring routed in
conduit with power must be 300V rated. For runs longer than 10 meters, signal separation from power is recommended to
minimize signal interference.
Disclaimer:
Manufacturer supplied components represented here are limited to the PCS/Battery, Evolve Hub, and CTs for PV, battery, and mains. All
other materials and components represented are customer supplied. CEC/NEC electrical code compliance is the responsibility of the
designer and/or electrical permit holder. Source circuit disconnects for PV and Evolve grid/load ports not shown.
Figure 9: Installation conduit plan for a solar plus storage installation (Evolve LFP base model shown)..