15
8 Technical Data
8.1 Electrical specifications
Note: About these ratings -
The Evolve Hub is a peripheral component of the Evolve ESS / LFP. It is a power distribution center with an on-
board energy management system. As such, this product is defined under the category of Interconnection System Equipment (ISE) for use
in utility interactive and/or stand-alone power systems under the scope of the UL1741 Standard, and is intended to be operated in parallel
with an electric power system (EPS) to supply power to common loads. The Evolve Hub as a standalone device does not provide grid-
interactive functionality. Where necessary, the ratings included below are listed both as a standalone product, as well as in conjunction with
the Standard for Interconnecting Distributed Resources With Electric Power Systems, IEEE 1547, and the Standard for Conformance Test
Procedures for Equipment Interconnecting Distributed Resources with Electric Power Systems, IEEE 1547.1.
AC ratings – Power distrubution circuits
Nominal Grid voltage
240V/120V split phase
Nominal Grid frequency
60 Hz
Maximum continuous operating current (or Rated
current), AC
40.0 Amps
Maximum continuous operating power (or Rated
power), VA
9600 VA
Maximum AC fault current and duration (short circuit)
14.0 Apk, 2.5 Arms (duration 63.5 ms)
AC connections, number - type
4 – Grid, Load, PCS Grid, PCS Load
AC voltage operating range
Max: 100 to 264 Vac. Note: UL 1741SA compliant operating limits are
determined by the Evolve ACB05U-LP configuration settings
AC frequency operating range
Max: 47 to 63 Hz. Note: UL1741SA compliant operating limits are determined
by the ACB05U-LP configuration settings
Maximum output overcurrent rating, grid & backup
connection
40.0 Amps
Protective Class (I, II, or III)
Class I
Over-Voltage Category (OVC I, II, III, or IV)
OVC III
Pollution Degree
3
Lightning protection
IEEE 62.41.2, location category B, low exposure
General data
Width x height x depth
15.3” x 17.3” x 6.7” (389 x 440 x 170 mm)
Weight
23 lbs (10.5 kg)
Protection type
Type 3R
Ambient temperature, relative humidity, altitude
-20 °C to +50 °C, 95%, 2000 m
Cooling method
Convection
Installation type
Wall-mount (upright)
Enclosure material
Halogen free, self extinguishing fiberglass reinforced polyester
For use only with Eguana Evolve ESS & LFP energy storage systems
8.2 Wire and torque ratings
Use solid copper only, 90 °C or higher rating
PCS (AC)
# conductors
AWG
(min to max)
Torque
AC grid, load
3 con PE
10 AWG to 6 AWG
Push-lock, spring cage
AC PCS grid, PCS load
3 con PE
10 AWG to 6 AWG
Push-lock, spring cage
Ground Lug
1 conductor
10 AWG to 6 AWG
15.9 in-lbs
Optional breakers
2 pole
10 AWG to 6 AWG
17.7 in-lbs