EGS Appleton JBR Series Instruction For Installation And Maintenance Download Page 7

EGS Electrical Group • 800-621-1506 • www.appletonelec.com

330112 Rev. D 05/31/06   

Page 7 

B. DISCONNECT  SWITCH:

  Disconnect switches occasionally fail and need to be replaced. The disconnect switch utilized in this receptacle can be 

replaced with the same type and brand as factory installed. Doing so will not affect the U.L. Listing.

TO REPLACE DISCONNECT SWITCH:

 • 

Referring to "Figure A", loosen the line and load sides of disconnect switch pressure screws (13) and remove line side 

wires (10) and load side wires (7) from switch (11).

 • 

Remove disconnect switch by removing disconnect switch mounting screws (12). Remember the orientation of the

handle (9) with respect to the switch position. The handle must indicate that the receptacle is "OFF" when the disconnect 
switch is in the "OFF" position.

 • 

Replace the disconnect switch with the same type as shown in "Table F", reversing the steps taken to remove it. Make 

sure to reconnect the wires to the same locations as before disassembly.

 • 

Torque the disconnect switch mounting screws (12) to 10-14 in-lbs to fasten switch to mounting brackets (14).

 • 

Torque the disconnect switch pressure screws (13) to 12-15 in-lbs to hold wires in place.

 • 

Conduct tests as detailed in section 6, page 6 of these instructions.

C.  MOUNTING FEET (WITH ASSEMBLY NOT MOUNTED):

 

• Referring to "Figure G", remove mounting feet 

 

  screws from the back of the mounting feet assemblies (1).

 

• Replace mounting feet with new ones as shown in "Table G".

 

• Tighten mounting feet screws to 25-30 in-lbs torque.

D.  COVER AND HOUSING HINGES (WITH RECEPTACLE COVER CLOSED):

 

• Referring to "Figure G", loosen and remove housing hinge bolts.  Replace old hinge assemblies with the new 
assemblies (2) as shown in "Table G".  Make sure to properly align new hinge.  Tighten all hinge screws to 
25-32 in-lbs torque.

E. TERMINAL BLOCK:

 

• Referring to "Figure G", loosen terminal block lug

 

  screws and remove wires (7) from lugs.

 

• Remove terminal block mounting screws and remove terminal block from housing.

  • Replace the terminal block assembly (5) with a new one as speci

fi

 ed in "Table G" by reversing the 

  steps taken to remove it.

 

• Torque terminal block mounting screws to 8-12 in-lbs to fasten to housing.

 

• Replace wires (7) into the same lug locations as removed from the old terminal block.  Torque terminal block
  lug screws to the value shown in "Table A", depending on wire size.  Make sure wires are securely fas-
tened.

F. GROUND LUG:

 

• Referring to "Figure G" , loosen ground lug screw and remove ground wire from lug.

 

• Remove ground lug mounting screw from housing.

  • Replace ground lug and mounting screw assembly (7) with the appropriate one shown in "Table G".

• Torque ground lug mounting screw to 16-20 in-lbs to fasten to housing.

 

• Reconnect ground wire to lug and tighten ground lug screw to 30-40 in-lbs torque.

 It is recommended that an electrical preventive maintenance program such 
as found in the National Fire Protection Bulletin NFPA No. 70B, be followed in 
addition to the above.

TABLE F: DISCONNECT SWITCHES

Disconnect Switch Part Number

AMP Ratings 

(AMPS)

Number of 

Poles

Appleton

Bryant

Hubbell

501734

30002

7832

30

2

501735

30003

7810UD

30

3

301607

60002

7862

60

2

301608

60003

7863

60

3

Summary of Contents for Appleton JBR Series

Page 1: ...with receptacle when switch is ON E Positive contact Brass contacts have integral springs for positive maintained electrical contact F Receptacle face enables the engagement of plugs for a weatherproo...

Page 2: ...fatal injuries due to electrocution WIRING WARNING A wire scheme must be followed so that the same color wire is always put into the same numbered contact open ing in all plugs connectors and receptac...

Page 3: ...JBR RECEPTACLE WITH SCREW COVER NOT SHOWN DRILLING PLANS FOR MOUNTING BOLTS 4 KEY HOLE SLOTS FOR 3 8 BOLTS 10 18 25 9 CM 3 75 9 5 CM 11 75 29 8 CM 13 27 33 7 CM 3 53 9 0 CM LOCKOUT HOLE CONDUIT ENTRY...

Page 4: ...e assembly on the previously prepared mounting bolts with the receptacle face 1 at the lower most position see Figure A Make sure that the shank of each of the bolts is in the small part of the key ho...

Page 5: ...t apply power until the following steps are completed A Test to verify correct phasing and ground connections B Test insulation resistance by meggering high voltage or hi pot test to be sure the syste...

Page 6: ...eptacle D A hole is provided in the receptacle cover for the use of padlocks see Figure B to lockout unauthorized movement of the handle 9 from the OFF position 11 MAINTENANCE A Receptacle must be ins...

Page 7: ...25 30 in lbs torque D COVER AND HOUSING HINGES WITH RECEPTACLE COVER CLOSED Referring to Figure G loosen and remove housing hinge bolts Replace old hinge assemblies with the new assemblies 2 as shown...

Page 8: ...eather shown in Table G if desired Apply grease to threads of drain and breather as previously stated in this instruction sheet Install the drain and breather and turn in until snug and then 1 2 turn...

Page 9: ...ver Assembly 350417 G 1 60 3W 4P Screw Cover Assembly 350420 G 1 4 30 2 Pole Disconnect Switch 501734 1 30 3 Pole Disconnect Switch 501735 1 60 2 Pole Disconnect Switch 301607 1 60 3 Pole Disconnect S...

Page 10: ...UD TYP TERMINAL BLOCK MOUNTING SCREW TYP 4 REQD TERMINAL BLOCK LUG SCREW TYP TERMINAL BLOCK LUG SCREW TYP RECEPTICAL HOUSING CLOSE UP PLUG CLOSE UP PLUG MOUNTING FEET SCREW TYP RECEPTICAL WITH FLIP CO...

Reviews: