EGS Appleton JBR Series Instruction For Installation And Maintenance Download Page 5

EGS Electrical Group • 800-621-1506 • www.appletonelec.com

330112 Rev. D 05/31/06   

Page 5 

INSTALLATION INSTRUCTIONS FOR:

"JBR" RECEPTACLE:  30AMP & 60AMP

C.  On all conduits, reducer bushings and close-up plugs, grease must be used to completely seal out water.
  • Appleton Electric, LLC thread lubricant, part number TLC-3 is recommended to be applied on threads in 

--three generous lines running parallel to the thread axis and spaced equidistant around the thread.

D.  Conduits and close-up plugs must be turned in until snug and then 1/2 turn further with a wrench.
 

• Do not over-tighten as damage to the housing threads or reducer bushings may occur.

 

• Make sure any installed breathers and drains are tightened in the same manner.

E.  At this point ensure that all threaded holes in the housing are closed to prevent entry of rain, splashed water, 

and hose directed water, and also to comply with Class I and Class II hazardous location requirements.

 

• This includes openings for breathers and drain.

5. WIRING:

A.  Referring to "Figure B", feed power supply wiring into hous-

ing (4) through conduit entries.

B.  Strip the individual conductors per "Table E".
C.  Connect wires to the proper terminal block lug (5) location by loosening (but not removing) terminal block 

set screw (6). Insert conductors including all strands into lugs according to your established wiring scheme.  
Tighten set screws (6) to the appropriate value shown in "Table A".  Please note the wire markers on the wires 
(7) connected between the disconnect switch and terminal block lugs (5).  These wire markers correspond to 
the contact identi

fi

 cation markings found on the back of the receptacle contact block.

6. ELECTRICAL TESTING:

  All wiring must be checked and tested to ensure that all circuits are according to plan and that there are no 

unwanted opens, shorts or grounds.  Do not apply power until the following steps are completed:

A.  Test to verify correct phasing and ground connections.
B.  Test insulation resistance by meggering, high voltage or hi-pot test, to be sure the system does not have any 

short circuits or unwanted grounds.

7.  CLEAN RECEPTACLE COVER AND HOUSING:

  Before replacing or closing the receptacle cover, it is strongly recommended that all dirt, debris and other 

foreign materials be removed from the housing interior.

  • This action should be taken to help keep the breathers and drains from being plugged by these materials.
  • Make sure the housing 

fl

 ange surface is clean. Wipe it with a clean, dry cloth to remove any foreign   

materials.

  • Clean the mating surface of the receptacle cover in the same manner while being careful not to damage  

 the gasket.

8. REPLACE RECEPTACLE COVER:

A. If the receptacle cover was removed, carefully rehang the cover on the hinges while the cover is positioned 

approximately 90 degrees from the housing.

B. Referring to "Figure A", connect the wires (7) that are leading out of the disconnect switch to the terminal 

block lugs (5) in ascending order from left to right. Note the wire markers that are on these wires. Each of 
these is numbered to correspond to the phase identi

fi

 cation numbers. Torque each terminal block lug 

screw (6) to the value shown in "Table A", depending on wire size used.

WARNING

•  "JBR" Receptacle is designed and tested for use with 

copper conductors only.

•  DO NOT USE ALUMINUM WIRING 

as dangerous over-

heating and 

fi

 re may result.

WARNING

Electrical power must be turned "OFF" before and during 
installation and maintenance.

FAILURE TO DO SO MAY RESULT IN SERIOUS OR FATAL 

INJURIES DUE TO ELECTROCUTION.

TABLE E

DIMENSIONS IN INCHES TEMINAL WIRE 
RANGE ANS STRIPPING GUIDE

Marathon Terminal Block

Ampere Rating

Strip Length 

(Inch)

Terminal Wire 

Range (AWG)

Torque Value

30

1/2

#10 - #6

35-45

60

5/8

#6 - #2

45-50

Eagle Terminal Block

Ampere Rating

Strip Length 

(Inch)

Terminal Wire 

Range (AWG)

Torque Value

30

3/8

#10 - #6

20-35

60

3/8

#6 - #4

20-35

Summary of Contents for Appleton JBR Series

Page 1: ...with receptacle when switch is ON E Positive contact Brass contacts have integral springs for positive maintained electrical contact F Receptacle face enables the engagement of plugs for a weatherproo...

Page 2: ...fatal injuries due to electrocution WIRING WARNING A wire scheme must be followed so that the same color wire is always put into the same numbered contact open ing in all plugs connectors and receptac...

Page 3: ...JBR RECEPTACLE WITH SCREW COVER NOT SHOWN DRILLING PLANS FOR MOUNTING BOLTS 4 KEY HOLE SLOTS FOR 3 8 BOLTS 10 18 25 9 CM 3 75 9 5 CM 11 75 29 8 CM 13 27 33 7 CM 3 53 9 0 CM LOCKOUT HOLE CONDUIT ENTRY...

Page 4: ...e assembly on the previously prepared mounting bolts with the receptacle face 1 at the lower most position see Figure A Make sure that the shank of each of the bolts is in the small part of the key ho...

Page 5: ...t apply power until the following steps are completed A Test to verify correct phasing and ground connections B Test insulation resistance by meggering high voltage or hi pot test to be sure the syste...

Page 6: ...eptacle D A hole is provided in the receptacle cover for the use of padlocks see Figure B to lockout unauthorized movement of the handle 9 from the OFF position 11 MAINTENANCE A Receptacle must be ins...

Page 7: ...25 30 in lbs torque D COVER AND HOUSING HINGES WITH RECEPTACLE COVER CLOSED Referring to Figure G loosen and remove housing hinge bolts Replace old hinge assemblies with the new assemblies 2 as shown...

Page 8: ...eather shown in Table G if desired Apply grease to threads of drain and breather as previously stated in this instruction sheet Install the drain and breather and turn in until snug and then 1 2 turn...

Page 9: ...ver Assembly 350417 G 1 60 3W 4P Screw Cover Assembly 350420 G 1 4 30 2 Pole Disconnect Switch 501734 1 30 3 Pole Disconnect Switch 501735 1 60 2 Pole Disconnect Switch 301607 1 60 3 Pole Disconnect S...

Page 10: ...UD TYP TERMINAL BLOCK MOUNTING SCREW TYP 4 REQD TERMINAL BLOCK LUG SCREW TYP TERMINAL BLOCK LUG SCREW TYP RECEPTICAL HOUSING CLOSE UP PLUG CLOSE UP PLUG MOUNTING FEET SCREW TYP RECEPTICAL WITH FLIP CO...

Reviews: