GCU -DG4 Manual
EGCON CO., LTD
(7)
1. Over current setting menu
2. Number 180 will blink in the second line of the display
when pressed <ENT>
3. Change setting values by using <UP> and <DOWN>
4. Press <ENT>
5. Number 5 in the third line of the display will blink.
6. Change setting values by using <UP> and <DOWN>
7. Changed setting will be saved when pressed <ENT>.
8. Over current setting range 2.0~ 6.5A
9. Waiting time setting range 1~60 seconds
(8)
1. Ground over current setting menu
2. Number "2.5" will blink in the second line of display when
<ENT> is pressed.
3. Change setting values by using <UP> and <DOWN>
4. Press <ENT>
5. Number "5.0" in the third line of the display will blink.
6. Change setting values by using <UP> and <DOWN>.
7. Changing will complete when <ENT> is pressed.
8. Setting range of ground over current : 0.2 ~ 5.0A
초
9. Setting range of waiting time : 0.1 ~ 6.0
.
(9)
1. RS485 communication setting menu
2. Number
will blink in the second line of display when
<ENT> is pressed.
3. Change setting value by using <UP> and <DOWN>.
4. Press <ENT>.
5. Number "1" will blink in the third line of display.
6. Change setting value using <UP> and <DOWN>.
7. Changing will complete when <ENT> is pressed.
8. Setting communication speed : - 9600 <
>
- 19200 <
>
- 38400 <
>
9. Setting range of address : 1 ~ 32