GCU -DG4 Manual
EGCON CO., LTD
Settings
▶
[1. ENGINE SET Switch] --> [ 5. OTU ] : Whether to use oil temperature gauge
[ 6. COM PWR ] : Whether to directly connect commercial power
[ 7. Method of detecting generator speed ] : VOLT, MPU
- VOLT : Detect generator speed from voltage of generator
- MPU : Detect generator speed using Magnet Pick Up sensor
[ 8. Engine operation method ] : ETS, ETR
[2. CT RATIO ] : CT setting
CT Ratio 1, CT Ratio 2, CT Ratio 3 usage setting
When using CT 1000/5 : CT Ratio 1 - 2, CT Ratio 2 - 0, CT Ratio 3 - 0 setting
Set values by Dividing CT 1000 by 5
When CT setting is different it displays different current value and voltage value
[3. OPT, WTG gauge setting ] --> set according to the settings menu
9. Regulator
9.1. TEST SW : Breakdown test button set to breakdown test selection
When this button is pressed it becomes the selected breakdown test regardless the actual breakdown
9.2. TIMER DIP S/W
DIP S/W number
1
2
3
4
Waiting time
for starting
○
○
3 Sec
○
●
5 Sec
●
○
10 Sec
●
●
30 Sec
Waiting time
for engine cool down
○
○
10 Sec
○
●
30 Sec
●
○
1 Min
●
●
3 Min
DIP S/W number
5
6
7
8
Waiting time for block
circuit breaker
○
○
3 Sec
○
●
5 Sec
●
○
10 Sec
●
●
30 Sec
Waiting time for input
of circuit breaker
○
○
3 Sec
○
●
5 Sec
●
○
10 Sec
●
●
30 Sec
: DIP S/W OFF,
: DIP S/W ON
○
●