 6

 

 

 

SMS Mode 

 

3. Notification about low battery voltage  

 
Before using this alarm the trigger voltage has to be set 
using the 

“setvolt”

 command. 

 

“setvolt”

:  When the battery voltage drops below this 

value the GSM-2-SMS modem sends an alarm SMS 
message (default value is 0.0). 
Example:  
12345:setvolt:11.8  
Set low voltage alarm trigger to 11.8 Volt (use decimal 
point)

  

 

“addvolt”

: add alarm recipient  

Example:  
12345:addvolt:0170123333  
Activate „low voltage“ message to phone number 
0170123333  
 

“delvolt”

: add alarm recipient 

Example:  
12345:delvolt:0170123333  
Deactivate „low voltage“ message to phone number 
0170123333  
 

4. Master alarm (all alarms) 

 
The 

„addall“

 command will send an alarm message to 

the defined recipients if any of the 3 alarm types occur. 
 

“addall”

: add master alarm recipient  

Example:  
12345:addall:0170123333  
Activate to send “all alarms “to phone number 
0170123333 
 

“delall”

: delete master alarm recipient 

Example:  
12345:delall:0170123333 
Deactivate to send “all alarms “to phone number 
0170123333 
 

5. Switch back to default settings 
 
„default“

: switch back to default settings. 

Example: 
12345:default: 
All alarm recipients will be deleted and no alarms will be 
sent 

  

Reset of EFOY-PRO: 

 

 

EFOY-PRO status request via SMS 

You can request the actual status of the EFOY-
PRO fuel cell via the following command. 
Example: 
12345:sfc:sfc – the GSM-2-SMS will return the 
current status of the EFOY-PRO fuel cell via 
SMS to your mobile phone. 
Example: 
SFC>SFC

 

battery voltage: 12.08V 
output current: 0.0A 
operating time: 5.8h 
operating state: error 
operating mode: auto 
please change fuel cartridge 
cartridge level below sensor 
SFC> 
 

Modem connection with EFOY-PRO fuel 
cell: 

 
The GSM-2-SMS modem offers a direct 
connection to the data interface of the EFOY-
PRO device using a standard terminal 
program such as Hyper Terminal.  
 
Establish a dial up connection between the 
GSM-2-SMS modem and your PC modem.  
 
Use communication settings 9600 bits/s, 
8bits/byte, 1 stop bit, no parity, no flow control. 
 
Example: 

ATD016045678 

 
After a successful connection with the GSM-2-
SMS modem (

“CONNECT…”

) please enter the 

last 5 digits of the GSM-2 IMEI number.  
 
In case the authorization has been successful 

“ok“

 will be prompted and a direct 

communication link has been established with 
the serial data communication interface of the 
EFOY-PRO unit (see more details in the 
computer interface adapter manual).  
 
In case the authorization fails 

“bye“

 will be 

prompted and the connection is cancelled by 
the GSM-2-SMS modem.  
 

Summary of Contents for GSM-2-SMS

Page 1: ......

Page 2: ......

Page 3: ...pe Installation Operation SMS Mode Modem connection GPRS Mode Annex Bedienungsanleitung Deutsch Einleitung und Hinweise Lieferumfang Installationshinweise Betrieb Konfiguration via SMS Terminalverbind...

Page 4: ...RJ45 DIN Rail holder GSM antenna Installation manual Installation Step 1 Insert SIM Card For operation a standard SIM card is required Mini SIM card 1 8 volt or 3 volt Important Before installing the...

Page 5: ...l Step 4 Connect power supply Connect the GSM 2 SMS to a DC power source with correct polarity using the power supply cable Pin6 GND Pin1 VCC The GSM 2 power supply voltage range is 8 30VDC The GSM 2...

Page 6: ...cmd command value command value You find the IMEI number on a sticker at the GSM 2 SMS Configuration of alarms There are 3 different alarm types 1 System error 2 Low fuel cartridge level requires fue...

Page 7: ...larms will be sent Reset of EFOY PRO EFOY PRO status request via SMS You can request the actual status of the EFOY PRO fuel cell via the following command Example 12345 sfc sfc the GSM 2 SMS will retu...

Page 8: ...om remote This can help to restart the unit if it has an uncritical error reset Reset of EFOY PRO fuel cell Example 12345 reset To disconnect a properly setup communication with the EFOY PRO fuel cell...

Page 9: ...in the SMS mode Additionally it is possible to send the alarm messages as email Configuration of GPRS mode The configuration is easily done via the Web portal with a standard Internet Web browser Requ...

Page 10: ...RXD Reveice Data 3 TXD Transmit Data 4 Not used 5 GND Signal ground 6 Not used 7 Not used 8 Not used 9 Not used Power Demand Parameter Min Typic al Max Unit Input voltage 8 12 30 VDC Max peak current...

Page 11: ...Sie eine Standard SIM Karte Mini SIM Karte 1 8 Volt oder 3 Volt WICHTIG Vor Erstinbetriebnahme muss die Pinabfrage der SIM Karte deaktiviert sein oder die Pin muss 1538 Default Einstellung GSM 2 laut...

Page 12: ...itte den mitgelieferten 2 fach Adapter Schritt 4 Anschluss Spannungsversorgung Schlie en Sie das GSM 2 SMS Modem mit dem mit gelieferten Stromversorgungskabel polrichtig an eine Gleichspannungsquelle...

Page 13: ...ng bei niedriger Batteriespannung Schwellwert ist einstellbar F r jede Alarmart ist einstellbar an welche Empf nger die Meldung gesendet werden soll 1 Alarmierung bei EFOY PRO Error addalarm Alarmempf...

Page 14: ...ie durch Senden des RESET Befehls einen Neustart der EFOY PRO ausl sen reset Reset der EFOY PRO Beispiel 12345 reset Statusabfrage der EFOY PRO Brennstoffzelle Beispiel 12345 sfc sfc Mit diesem Befehl...

Page 15: ...14 Um die Verbindung zu beenden wie folgt vorgehen Eingabe Antwort OK Eingabe ath...

Page 16: ...tellungen zu ver ndern Auch in diesem Modus ist die Alarmierung ber SMS und zus tzlich ber Email m glich Konfiguration GPRS Modus Die Konfigurierung erfolgt komfortabel mit einem Webbrowser ber das In...

Page 17: ...ta 3 TXD Transmit Data 4 Nicht benutzt 5 GND Signalmasse 6 Nicht benutzt 7 Nicht benutzt 8 Nicht benutzt 9 Nicht benutzt Leistungsaufnahme Parameter Min Typ Max Unit Eingangsspannung 8 12 30 VDC Max S...

Page 18: ...17...

Page 19: ......

Page 20: ......

Reviews: