Battery
Mode
(50/60±0.1)Hz
Crest Factor
3:1
THD
≤2% with linear load
≤5% with non linear load
Battery
Voltage
±192V/±204V/±216V/±228V/±240VDC
(32 /34/36/38/40PCS)
Charge Current(A)
max
30
40
50
Transfer Time
Utility to Battery : 0ms; Utility to bypass: 0ms
Protection
Overload
AC Mode
Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last
1min,
≥150% change to bypass.
Bat. Mode
Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last
1min,
≥150% shut down UPS.
Bypass
Mode
250A
315A
400A
Short Circuit
540A Peak
720A Peak
900A Peak
Overheat
Line Mode: Switch to Bypass; Backup Mode: Shut down
UPS immediately
Battery Low
Alarm and Switch off
Self-diagnostics
Upon Power On and Software Control
EPO(optional)
Shut down UPS immediately
Model
Capacity
100kVA
90kW
120kVA
108kW
160kVA
144kW
200kVA
180kW
Protection
Battery
Advanced Battery Management
Noise Suppression
Complies with EN62040-2
Communication Interface
USB, RS485,Parallel,SNMP card(optional),Relay
card(optional)
Environment
Operating
Temperature
0
℃
~
40
℃
Storage
Temperature
-25
℃
~
55
℃
Humidity
0
~
95% non condensing
Altitude
< 1500m
Display
Audible & Visual
Line Failure, Battery Low, Overload, System Fault
Status LED & LCD
Line Mode, Bypass Mode, Battery Low, Battery Bad,
Overload & UPS Fault
Reading On the LCD
Input Voltage, Input Frequency, Output Voltage, Output
Frequency, Load Percentage, Battery Voltage, parameter
set, history record
…
Other
Unit
Dimensions(W*D*H)
600*850*1600
Weight (Kg)
345
379
413
Safety Conformance
CE,EN/IEC 62040-2,EN/IEC 62040-1-1