background image

 

A manual bypass switch is available to ensure continuity of supply to the critical load when the 

UPS is out of order or in repair and this manual bypass switch bears for equivalent rated load.   

 

4.2 Turn on/off UPS 

4.2.1

 

Restart procedure

 

CAUTION!

 

MAKE SURE GROUNDING IS PROPERLY DONE!

 

 Set the Battery Breaker to the 

“ON” position according to the user’s manual.     

 Open the front and rear doors of the UPS to access to the main power switches. During 

this procedure the output terminals will become alive.

 

 

CAUTION

 

Check to see if the load is safely connected with the output of the UPS. If the 

load  is  not  ready  to  receive  power  from  the  UPS,  make  sure  that  it  is  safely 

isolated from the UPS output terminals 

CAUTION!

 

Be sure that the maintenance cover is closed well before turn on the UPS!

 

 

 UPS Input Switch (below the UPS module at the front door)   

 

If the Rectifier input is within voltage range, the rectifier will start up in 30 seconds then 

the inverter will start up after then.     

 UPS Output Switch (below the UPS module at the front door)     

 

If the rectifier fails at startup, the bypass LED will light up.    When the inverter starts up, 

the  UPS  will  transfer  from  bypass  mode  to  inverter  mode,  and  then  the  bypass  LED 

extinguishes and the inverter LED lights up.     

No matter whether the UPS can work normally or not, all the status will be shown on the 

LCD display.     

4.2.2 Test procedure 

 

CAUTION!

 

The UPS is operating normally. 

It may take 60 seconds to boost up the system and perform self-test completely.   

  Switch  off  the  MAINS  to  simulate  utility  failure,  the  rectifier  will  turn  off  and  the  battery 

Summary of Contents for TRITON M3

Page 1: ...UPS Uninterruptible Power Supply TRITON M3 100 200 kVA Operating Manual V 1 0 Article Numbers ACX33TRS100Kxxxx ACX33TRS120Kxxxx ACX33TRS160Kxxxx ACX33TRS200Kxxxx...

Page 2: ...able connect 12 3 8 Battery connection 13 3 9 UPS Multi Module Installation 14 3 10 LBS installation 15 4 Operation 17 4 1 Operation Modes 17 4 2 Turn on off UPS 18 4 3 The Display 21 4 4 Options 25 A...

Page 3: ...trongly poisonous and do harmful to body 4 Please avoid short circuit between anode and cathode of battery otherwise it will cause spark or fire 5 Don t disassemble the UPS cover or there may be an el...

Page 4: ...ry voltage of this series UPS can be configured at 32 blocks 34 blocks 36 blocks 38 blocks or 40 blocks according to your convenience Charging Current is configurable The user may set the capacity of...

Page 5: ...ce to see if the UPS is damaged or not during the transportation do not switch on the UPS if any damage found Please contact the dealer right away 3 Check the accessories according to the packing list...

Page 6: ...HIP33100 33120 Front View internal Rear View internal...

Page 7: ...HIP33160 Front View internal Rear View internal...

Page 8: ...ss switch cover plate Remove cover to operate bypass switch 5 Dustproof net plate 6 Fuse Box Input fuses and Battery fuses inbuilt box 1 connected to module 1 7 Communication panel 8 I P Switch 9 Main...

Page 9: ...ort 1 Communication panel fixed screw 2 Intelligent slot 1 insert SNMP card or Dry contact card 3 Intelligent slot 2 insert SNMP card or Dry contact card 4 RS485 port 1 2 5 BAT_T port 1 2 connect batt...

Page 10: ...1 6 Dustproof net plate fixed screw...

Page 11: ...antled under low temperature it might be in a condensing condition The UPS can t be installed unless the internal and external of the equipment is fully dry Otherwise there will be in danger of electr...

Page 12: ...ver current through a DC compatible thermo magnetic circuit breaker or a set of fuses located close to the battery UPS Output Any external distribution board used for load distribution shall be fitted...

Page 13: ...solated from its external power source and also all power isolators of the UPS are open Check to see if they are electrically isolated and post any necessary warning signs to prevent their inadvertent...

Page 14: ...and national codes of practice 3 8 Battery connection The UPS adopts positive and negative double battery framework total 32 optional 34 36 38 40 in series A neutral cable is retrieved from the joint...

Page 15: ...on I e inter tier and inter block connections are from to terminals Don t mix batteries with different capacity or different brands or even mix up new and old batteries either WARNING Ensure correct p...

Page 16: ...ake sure the N A L1 B L2 C L3 lines are correct and grounding is well connected 3 9 2 Parallel cable installation Shielded and double insulated control cables available must be interconnected in a rin...

Page 17: ...its LBS setting must be set to Master 3 10 2 LBS cable installation The two ports of one mesh wire should be plug into RJ45 interface of any one UPS of both master and slave system 3 10 3 UPS install...

Page 18: ...void paralleling of unsynchronized AC sources This interruption is programmable but typically set to be less than an electrical cycle e g less than 15ms 50Hz or less than 13 33ms 60Hz ECO Mode When th...

Page 19: ...ut terminals CAUTION Be sure that the maintenance cover is closed well before turn on the UPS UPS Input Switch below the UPS module at the front door If the Rectifier input is within voltage range the...

Page 20: ...s not conditioned Switch to mechanical bypass CAUTION If the UPS is running normally and can be controlled through the display carry out steps 1 to 5 otherwise jump to Step 4 Open the cover of mainten...

Page 21: ...start button of the module as the position 5 of the above drawing When battery normal rectifier starts operation 30s later inverter starts and operates and battery LED on CAUTION Wait for approximatel...

Page 22: ...Wait for about 5 minutes for the internal D C bus bar capacitors to be completely discharged 4 3 The Display 4 3 1 LCD display Introduction CAUTION The display provides more functions than those desc...

Page 23: ...TURN TO BYPASS CONFIRM TURN TO BYPASS BYPASS MODE TURNING OFF SELFTEST SELFTEST UPS TESTING INQUIRE INQUIRE DETAIL INQUIRE OUTPUT INQUIRE INPUT...

Page 24: ...INQUIRE BATTERY INQUIRE LOAD INQUIRE ALARM OFF INQUIRE ALARM ON INQUIRE SERVICE USER SETUP PASSWORD USER SETUP TIME SET USER KEY SET LANGUAGE SET Alarm Information...

Page 25: ...t Beep continuously Fault LED lit 15 DC Bus over voltage Beep continuously Fault LED lit 16 DC Bus below voltage Beep continuously Fault LED lit 17 DC bus unbalance Beep continuously Fault LED lit 18...

Page 26: ...rew unlock 45 UPS not work 4 4 Options SNMP card internal SNMP external SNMP optional Loosen the 2 torque screws on each side of the card Carefully pull out the card Reverse the procedure for re insta...

Page 27: ...e 40Hz 70Hz Power Factor 0 99 Current THDi 3 100 nonlinear load Bypass Voltage Range Max voltage 220V 25 optional 10 15 20 230V 20 optional 10 15 240V 15 optional 10 Min voltage 45 optional 20 30 Freq...

Page 28: ...On and Software Control EPO optional Shut down UPS immediately Model Capacity 100kVA 90kW 120kVA 108kW 160kVA 144kW 200kVA 180kW Protection Battery Advanced Battery Management Noise Suppression Compl...

Page 29: ...using this UPS in the right way Some FAQ frequently asked questions may help you to troubleshoot your problem easily No Problem Possible reason Solution 1 Utility is connected but the UPS can not be p...

Page 30: ...hole group batteries Connect the battery cables correctly Go to LCD setting of the battery number and capacity set the correct data 7 Buzzer beeps every 0 5 seconds and LCD display output overload Ove...

Page 31: ...Connection between PC RS232 port and UPS RS232 port PC RS232 port UPS RS232 port Pin 2 Pin 2 UPS send PC receive Pin 3 Pin 3 PC send UPS receive Pin 5 Pin 5 ground Available function of RS232 Monitor...

Page 32: ...e same time Appendix 4 USB communication port definition Definition of USB port Connection between PC USB port and UPS USB port PC USB port UPS RS232 port Description Pin 1 Pin 1 PC 5V Pin 2 Pin 2 PC...

Page 33: ...Timing off on setting USB communication data format Baud rate 2400bps Byte length 8bit End bit 1bit Parity check none CAUTION USB RS232 RS485 ports cannot be used at the same time...

Page 34: ...5 Description Pin 1 5 Pin 1 5 485 A Pin 2 4 Pin 2 4 485 B Available function of RS485 Monitor UPS power status Monitor UPS alarm info Monitor UPS running parameters Timing off on setting RS485 communi...

Page 35: ...4 Pin 2 4 LBS_TRACE_BC Pin 8 Pin 8 GND Available function of LBS The output power of two or more UPS in non parallel system should be synchronized with each other The output phase of two or more UPS i...

Page 36: ...on Pin 1 5 Pin 1 5 TX Pin 2 4 Pin 2 4 RX Pin 7 Pin 7 12V Pin 8 Pin 8 GND Connection between the BAT_T box port and UPS2 s BAT_T port UHTWSC3 Temperature sensor UPS2 BAT_T RJ45 Description Pin 2 Pin 1...

Page 37: ...Appendix 8 Drycontact port definition Definition of port Drycontact Description Pin 1 12V Pin 2 DRY_GENER Pin 3 DRY_BP_O Pin 4 DRY_BP_S...

Page 38: ...3 second the UPS also supports a remote emergency stop REPO A remote emergency stop switch Dry contact signal and normally open not provided can be installed in a remote location and connection throug...

Reviews: