background image

 

Event log   

UPS Alarm Warning 

Buzzer 

LED 

Rectifier Fault 

Beep continuously 

Fault LED lit 

Inverter 

fault(Including 

Inverter 

bridge is shorted) 

Beep continuously 

Fault LED lit 

Inverter Thyristor short 

Beep continuously 

Fault LED lit 

Inverter Thyristor broken 

Beep continuously 

Fault LED lit 

Bypass Thyristor short 

Beep continuously 

Fault LED lit 

Bypass Thyristor broken 

Beep continuously 

Fault LED lit 

Fuse broken 

Beep continuously 

Fault LED lit 

Parallel relay fault 

Beep continuously 

Fault LED lit 

Fan fault 

Beep continuously 

Fault LED lit 

10 

Reserve 

Beep continuously 

Fault LED lit 

11 

Auxiliary power fault 

Beep continuously 

Fault LED lit 

12 

Initializtion fault 

Beep continuously 

Fault LED lit 

13 

P-Battery Charger fault 

Beep continuously 

Fault LED lit 

14 

N-Battery Charger fault 

Beep continuously 

Fault LED lit 

15 

DC Bus over voltage 

Beep continuously 

Fault LED lit 

16 

DC Bus below voltage 

Beep continuously 

Fault LED lit 

17 

DC bus unbalance 

Beep continuously 

Fault LED lit 

18 

Soft start failed 

Beep continuously 

Fault LED lit 

19 

Rectifier Over Temperature 

Beep continuously 

Fault LED lit 

20 

Inverter Over temperature 

Twice per second 

Fault LED lit 

21 

Reserve 

Twice per second 

Fault LED lit 

22 

Battery reverse 

Twice per second 

Fault LED lit 

23 

Cable connection error 

Twice per second 

Fault LED lit 

24 

CAN comm. Fault 

Twice per second 

Fault LED lit 

25 

Parallel load sharing fault 

Twice per second 

Fault LED lit 

26 

Battery over voltage 

Twice per second 

Fault LED blinking 

27 

Mains Site Wiring Fault 

Once per second 

Fault LED blinking 

28 

Bypass Site Wiring Fault 

Once per second 

Fault LED blinking 

29 

Output Short-circuit 

Once per second 

Fault LED blinking 

30 

Rectifier over current 

Once per second 

Fault LED blinking 

31 

Bypass over current 

Once per second 

BPS LED blinking 

Summary of Contents for TRITON M3

Page 1: ...UPS Uninterruptible Power Supply TRITON M3 100 200 kVA Operating Manual V 1 0 Article Numbers ACX33TRS100Kxxxx ACX33TRS120Kxxxx ACX33TRS160Kxxxx ACX33TRS200Kxxxx...

Page 2: ...able connect 12 3 8 Battery connection 13 3 9 UPS Multi Module Installation 14 3 10 LBS installation 15 4 Operation 17 4 1 Operation Modes 17 4 2 Turn on off UPS 18 4 3 The Display 21 4 4 Options 25 A...

Page 3: ...trongly poisonous and do harmful to body 4 Please avoid short circuit between anode and cathode of battery otherwise it will cause spark or fire 5 Don t disassemble the UPS cover or there may be an el...

Page 4: ...ry voltage of this series UPS can be configured at 32 blocks 34 blocks 36 blocks 38 blocks or 40 blocks according to your convenience Charging Current is configurable The user may set the capacity of...

Page 5: ...ce to see if the UPS is damaged or not during the transportation do not switch on the UPS if any damage found Please contact the dealer right away 3 Check the accessories according to the packing list...

Page 6: ...HIP33100 33120 Front View internal Rear View internal...

Page 7: ...HIP33160 Front View internal Rear View internal...

Page 8: ...ss switch cover plate Remove cover to operate bypass switch 5 Dustproof net plate 6 Fuse Box Input fuses and Battery fuses inbuilt box 1 connected to module 1 7 Communication panel 8 I P Switch 9 Main...

Page 9: ...ort 1 Communication panel fixed screw 2 Intelligent slot 1 insert SNMP card or Dry contact card 3 Intelligent slot 2 insert SNMP card or Dry contact card 4 RS485 port 1 2 5 BAT_T port 1 2 connect batt...

Page 10: ...1 6 Dustproof net plate fixed screw...

Page 11: ...antled under low temperature it might be in a condensing condition The UPS can t be installed unless the internal and external of the equipment is fully dry Otherwise there will be in danger of electr...

Page 12: ...ver current through a DC compatible thermo magnetic circuit breaker or a set of fuses located close to the battery UPS Output Any external distribution board used for load distribution shall be fitted...

Page 13: ...solated from its external power source and also all power isolators of the UPS are open Check to see if they are electrically isolated and post any necessary warning signs to prevent their inadvertent...

Page 14: ...and national codes of practice 3 8 Battery connection The UPS adopts positive and negative double battery framework total 32 optional 34 36 38 40 in series A neutral cable is retrieved from the joint...

Page 15: ...on I e inter tier and inter block connections are from to terminals Don t mix batteries with different capacity or different brands or even mix up new and old batteries either WARNING Ensure correct p...

Page 16: ...ake sure the N A L1 B L2 C L3 lines are correct and grounding is well connected 3 9 2 Parallel cable installation Shielded and double insulated control cables available must be interconnected in a rin...

Page 17: ...its LBS setting must be set to Master 3 10 2 LBS cable installation The two ports of one mesh wire should be plug into RJ45 interface of any one UPS of both master and slave system 3 10 3 UPS install...

Page 18: ...void paralleling of unsynchronized AC sources This interruption is programmable but typically set to be less than an electrical cycle e g less than 15ms 50Hz or less than 13 33ms 60Hz ECO Mode When th...

Page 19: ...ut terminals CAUTION Be sure that the maintenance cover is closed well before turn on the UPS UPS Input Switch below the UPS module at the front door If the Rectifier input is within voltage range the...

Page 20: ...s not conditioned Switch to mechanical bypass CAUTION If the UPS is running normally and can be controlled through the display carry out steps 1 to 5 otherwise jump to Step 4 Open the cover of mainten...

Page 21: ...start button of the module as the position 5 of the above drawing When battery normal rectifier starts operation 30s later inverter starts and operates and battery LED on CAUTION Wait for approximatel...

Page 22: ...Wait for about 5 minutes for the internal D C bus bar capacitors to be completely discharged 4 3 The Display 4 3 1 LCD display Introduction CAUTION The display provides more functions than those desc...

Page 23: ...TURN TO BYPASS CONFIRM TURN TO BYPASS BYPASS MODE TURNING OFF SELFTEST SELFTEST UPS TESTING INQUIRE INQUIRE DETAIL INQUIRE OUTPUT INQUIRE INPUT...

Page 24: ...INQUIRE BATTERY INQUIRE LOAD INQUIRE ALARM OFF INQUIRE ALARM ON INQUIRE SERVICE USER SETUP PASSWORD USER SETUP TIME SET USER KEY SET LANGUAGE SET Alarm Information...

Page 25: ...t Beep continuously Fault LED lit 15 DC Bus over voltage Beep continuously Fault LED lit 16 DC Bus below voltage Beep continuously Fault LED lit 17 DC bus unbalance Beep continuously Fault LED lit 18...

Page 26: ...rew unlock 45 UPS not work 4 4 Options SNMP card internal SNMP external SNMP optional Loosen the 2 torque screws on each side of the card Carefully pull out the card Reverse the procedure for re insta...

Page 27: ...e 40Hz 70Hz Power Factor 0 99 Current THDi 3 100 nonlinear load Bypass Voltage Range Max voltage 220V 25 optional 10 15 20 230V 20 optional 10 15 240V 15 optional 10 Min voltage 45 optional 20 30 Freq...

Page 28: ...On and Software Control EPO optional Shut down UPS immediately Model Capacity 100kVA 90kW 120kVA 108kW 160kVA 144kW 200kVA 180kW Protection Battery Advanced Battery Management Noise Suppression Compl...

Page 29: ...using this UPS in the right way Some FAQ frequently asked questions may help you to troubleshoot your problem easily No Problem Possible reason Solution 1 Utility is connected but the UPS can not be p...

Page 30: ...hole group batteries Connect the battery cables correctly Go to LCD setting of the battery number and capacity set the correct data 7 Buzzer beeps every 0 5 seconds and LCD display output overload Ove...

Page 31: ...Connection between PC RS232 port and UPS RS232 port PC RS232 port UPS RS232 port Pin 2 Pin 2 UPS send PC receive Pin 3 Pin 3 PC send UPS receive Pin 5 Pin 5 ground Available function of RS232 Monitor...

Page 32: ...e same time Appendix 4 USB communication port definition Definition of USB port Connection between PC USB port and UPS USB port PC USB port UPS RS232 port Description Pin 1 Pin 1 PC 5V Pin 2 Pin 2 PC...

Page 33: ...Timing off on setting USB communication data format Baud rate 2400bps Byte length 8bit End bit 1bit Parity check none CAUTION USB RS232 RS485 ports cannot be used at the same time...

Page 34: ...5 Description Pin 1 5 Pin 1 5 485 A Pin 2 4 Pin 2 4 485 B Available function of RS485 Monitor UPS power status Monitor UPS alarm info Monitor UPS running parameters Timing off on setting RS485 communi...

Page 35: ...4 Pin 2 4 LBS_TRACE_BC Pin 8 Pin 8 GND Available function of LBS The output power of two or more UPS in non parallel system should be synchronized with each other The output phase of two or more UPS i...

Page 36: ...on Pin 1 5 Pin 1 5 TX Pin 2 4 Pin 2 4 RX Pin 7 Pin 7 12V Pin 8 Pin 8 GND Connection between the BAT_T box port and UPS2 s BAT_T port UHTWSC3 Temperature sensor UPS2 BAT_T RJ45 Description Pin 2 Pin 1...

Page 37: ...Appendix 8 Drycontact port definition Definition of port Drycontact Description Pin 1 12V Pin 2 DRY_GENER Pin 3 DRY_BP_O Pin 4 DRY_BP_S...

Page 38: ...3 second the UPS also supports a remote emergency stop REPO A remote emergency stop switch Dry contact signal and normally open not provided can be installed in a remote location and connection throug...

Reviews: