UPS RMH700/1000/1500
Instruction Manual
RMH Series
Page 21 of 37
8.1 Connecting the UPS
The RMH Series models are equipped with plug connections. The connection
diagram (Fig. 6) and the following information must be observed:
Fig. 6:
Connecting the
UPS
RMH700/
1000/1500
S: 10
A
1: 0,75
mm²
Warning
The UPS equipment contains components with high voltage and amperage.
Incorrect handling may therefore lead to electrical accidents, sometimes with
fatal consequences or material damage.
The protective earth conductor must be connected without fail! If not, the
consumer loads will also not be earthed.
If a generator is used to operate the equipment, the correct poling must be
observed when connecting the UPS.
Warning
The connection diagram shown in Fig. 6 only applies if:
o
the loop resistance is complied with up to the last consumer load;
o
earthing of the consumer loads is safely guaranteed;
o
or the consumer loads are separately protected against overcurrents and
leakage currents, and are also earthed.
If the UPS equipment is within an EMERGENCY-OFF circuit, it must be noted
that if this is activated, the UPS output will not de-energized. The consumer
loads will continue to be supplied for the duration of the support time.