6-­‐   SIZING   GUIDE   

Please   use   the   chart   below   to   see   how   many   gallons   per   minute   your   tankless   water   heater   can   produce   with   
your   incoming   water   temperature.   The   gallons   per   minute   is   calculated   assuming   105°F   outlet   temperature.   

   

Incoming   Water   

Temperature   

HA008240   

HA011240   

HA013240   

HA018240   

HA024240   

HA027240   

HA036240   

40°F   

0.8   

1.2   

1.4   

1.9   

2.5   

2.8   

3.8   

45°F   

0.9   

1.3   

1.5   

2.0   

2.7   

3.1   

4.1   

50°F   

1.0   

1.4   

1.6   

2.2   

3.0   

3.4   

4.5   

55°F   

1.1   

1.5   

1.8   

2.5   

3.3   

3.7   

4.9   

60°F   

1.2   

1.7   

2.0   

2.7   

3.6   

4.1   

5.5   

65°F   

1.4   

1.9   

2.2   

3.1   

4.1   

4.6   

6.1   

70°F   

1.6   

2.2   

2.5   

3.5   

4.7   

5.3   

7.0   

75°F   

1.8   

2.5   

3.0   

4.1   

5.5   

6.1   

8.2   

80°F   

2.2   

3.0   

3.6   

4.9   

6.6   

7.4   

9.8   

   

(Gallons   per   Minute)   

   

   
   

FLOW   REGULATOR   –   OPTIONAL   

To   ensure   the   optimal   temperature   output   and   overall   performance   of   your   tankless   water   heater   you   may   
require   a   flow   regulator.   These   flow   regulators   are   installed   on   the   outlet   connection   of   your   tankless   water   
heater   and   limit   the   maximum   volume   coming   out   of   your   unit   to   a   specified   flow   rate   to   prevent   the   exit   
temperature   from   becoming   too   cool.   To   learn   more   about   flow   regulators   or   find   out   how   to   purchase   one   for   
your   tankless   water   heater   visit   us   online   at   Eemax.com   or   contact   us   at   1-­‐800-­‐543-­‐6163.   

Steps   for   Choosing   a   Flow   Regulator   

1.

  

Find   your   model   in   the   chart   on   the   left   

2.

  

Choose   the   column   with   the   inlet   water   temperature   closest   to   your   geographical   location   

3.

  

Take   the   GPM   or   gallons   per   minute   you   find   and   match   it   with   the   corresponding   flow   regulator   on   the   
right   

                                       Inlet   Water   Temperature

   

   

40°F   

50°F   

60°F   

70°F   

   

Eemax   Part   Number   

Maximum   Flow   Rate   

Connection   Size   

HA008240   

1.0   

1.0   

1.0   

1.5   

IFR   1-­‐2   

1.0   GPM   

1/2"   Compression   

HA011240   

1.0   

1.0   

1.5   

2.0   

1.5   GPM   

1/2"   Compression   

HA013240   

1.0   

1.5   

2.0   

2.0   

2.0   GPM   

1/2"   Compression   

HA018240   

2.0   

2.0   

2.0   

3.0   

IFR   3-­‐4   

2.0   GPM   

3/4"   NPT   

HA024240   

2.0   

2.0   

3.0   

4.0   

3.0   GPM   

3/4"   NPT   

HA027240   

2.0   

3.0   

4.0   

5.0   

4.0   GPM   

3/4"   NPT   

HA036240   

3.0   

4.0   

5.0   

5.0   

5.0   GPM   

3/4"   NPT   

   

*Selection   based   on   inlet   temperature   above   and   outlet   temperature   of   105°F   

Summary of Contents for HA008240

Page 1: ...unit directly at the circuit breaker box SERIOUS BODILY INJURY OR DEATH COULD OCCUR IF YOU IGNORE THIS WARNING THIS PRODUCT SHOULD BE INSTALLED BY A QUALIFIED ELECTRICIAN AND A QUALIFIED PLUMBER IN ACCORDANCE WITH ALL NATIONAL STATE PROVINCIAL AND LOCAL ELECTRICAL PLUMBING CODES PLEASE READ THESE INSTRUCTIONS THOROUGHLY AND COMPLETELY PRIOR TO INSTALLATION USE FAILURE TO DO SO COULD CAUSE PROPERTY...

Page 2: ...g valve complying with the Standard for Temperature Actuated Mixing Valves for Hot Water Distribution Systems ASSE 1017 be installed The chart shown above may be used as a guide in determining the proper water temperature for your home DANGER Households with small children disabled or elderly persons may require a 120 F or lower thermostat setting to prevent contact with HOT water The temperature ...

Page 3: ...s at any time please contact us directly at Eemax Inc 400 Captain Neville Drive Waterbury CT 06705 Toll Free 1 800 543 6163 or 203 267 7890 Fax 203 267 7975 info eemaxinc com CONTENTS 1 BEFORE INSTALLATION 2 SELECTING A LOCATION TO INSTALL 3 MOUNTING YOUR WATER HEATER 4 PLUMBING INSTALLATION 5 ELECTRICAL INSTALLATION 6 SIZING GUIDE 7 GENERAL OPERATING INSTRUCTIONS 8 MAINTENANCE 9 TROUBLE SHOOTING ...

Page 4: ...cal boxes or junctions If you plan to install your water heater on a second floor or in a heated attic space make sure to follow all code requirements for such installations as required for your area We recommend that you install a drip pan connected to a safe drain below the water heater to avoid property damage in the unlikely event of a leak Alternatively you can install an active water leak de...

Page 5: ...s NOT require that a pressure relief valve be used However a T P valve may be required to meet installation codes in your area If one is required install the pressure relief valve in accordance with local codes and ensure that it operates correctly and that air is purged from the valve prior to installing the water heater When connecting to Flex or High Temperature CPVC pipe we recommend that a T ...

Page 6: ...nd see wiring diagram Model HA036240 requires 4 sets of wires and ground see wiring diagram Please see electrical specifications by model and wiring diagram on the next page for additional electrical information Each set of wires must be connected to its own individual double pole breaker Installation Instructions STEP 1 Take each wire pair and connect them to one breaker see wiring diagram Make s...

Page 7: ...50 AMPS REQUIRED BREAKERS 1 x 40 AMP 1 x 50 AMP 1 X 60 AMP 2 X 40 AMP 3 x 40 AMP 3 X 40 AMP 4 X 40 AMP REQUIRED WIRE GAUGE 1 x 8 AWG 1 x 6 AWG 1 x 6 AWG 2 X 8 AWG 3 x 8 AWG 3 X 8 AWG 4 X 8 AWG Wiring Diagram Circuit Breaker 1 L1 L1 Circuit Breaker 2 L2 L2 Circuit Breaker 3 L3 L3 Circuit Breaker 4 L4 L4 BLACK RED BLACK RED BLACK RED BLACK RED HA008240 HA011240 HA013240 require 1 set of breaker and ...

Page 8: ...ter and limit the maximum volume coming out of your unit to a specified flow rate to prevent the exit temperature from becoming too cool To learn more about flow regulators or find out how to purchase one for your tankless water heater visit us online at Eemax com or contact us at 1 800 543 6163 Steps for Choosing a Flow Regulator 1 Find your model in the chart on the left 2 Choose the column with...

Page 9: ...er leak we recommend the following maintenance Inspect the connections on the inlet and outlet of the water heater at least on an annual basis for any signs of damage or failure Any signs of damage cracks leakage or weakness should be addressed Take care not to over tighten the connections Serious internal damage to your water heater can occur if you over tighten the water heater connections at th...

Page 10: ...hat the wiring is incorrect Voltage less than 240 volts The heating elements on your water heater are design for 240 volts When used with a lower voltage they produce less heating power You may need to upgrade to a larger model Mixing too much cold water You do not need to mix as much cold water with your tankless water heater compared to when you use a conventional water heater You may also have ...

Page 11: ...ving the cover to change the temperature set point exposes electrical shock and burn hazards which can cause INJURY or DEATH Adjustment should only be done by a licensed plumber or electrician HA008240 HA011240 HA013240 HA018240 HA024240 HA027240 HA036240 1 Hot Water Outlet 5 Adjustment Knob Temperature Control 9 Electrical Strain Relief 2 Cold Water Inlet 6 Wire Connection 10 Mounting Bracket 1 3...