Pagina
21 di 24
Nr.
Funzione
Nome
Tipo
Flag
18, 19
ON/OFF/Toggle
Input X
EIS1, 1bit
DPT 1.001
C,R,T
Telegram Values “0” OFF
“1” ON
The switching telegrams of inputs 1 or 2 are sent via the group addresses associated to
these objects.
It is possible to select which signal edge detected at the input channels generate On or
Off telegrams via the parameters of the corresponding inputs.
With “Toggle” selection the object value is inverted (e.g. in case a push button is
connected to an input channel at every push button pressing the status is inverted
ON/OFF (or viceversa).
In case cyclical sending is enabled the current input value is transmitted to the bus at
every timing interval set with “Cycling Send Time (Min)” parameter (e.g. monitoring of a
physical sensor status with a Visualization software).
20
Power Fail alarm
Alarm
EIS1, 1bit
DPT 1.005
C,R,T
In case the parameter “Send Alarm” is set to “ON” than this object is shown.
This object are sent (“ON”) in case of device power falure as the power supply has been
recovered.
This alarm can be useful to a visualization and access control software to re-syncronized
data end time into all transponder readers (and holders) after a power failure or for
different purposes.