Pagina
20 di 24
Nr.
Funzione
Nome
Tipo
Flag
10
Set Plant ID
Build Number
EIS10, 2byte
DPT 7.001
C,W,T
The object “Build Number” is used to identify the installation or the building where the
transponder readers are installed.
This code avoid any possible risk of using the same card for entrance in two different
buildings. It is sent by the building management software during commissioning.
11
Password
Guest Data
NON EIS
10 byte
C,W,T
The object “Guest Data” is sent by the access control management software to the
transponder readers and holders in order to enable entrance and card identification once
the transponder card is read.
This object (non KNX standard object) contains the user password id, the expiration date,
the enabled timing entrance ranges, the valid entrance days of week and the expiration
data. After the “Build Number” reading and acceptance the transponder reader or holder
controls the password and any other information associated in order to allow or not allow
the room entrance.
“
Guest Data” object is normally sent during transponder readers and holders configuration
by the access control software (“eAccess” or “eHotel”).
12
Access Data
Access Code
EIS12, 4byte
DPT 15.000
C,T
This object is used to send to the bus the result of a transponder card reading.
Within this object the password and some reading feedbacks are sent to the centralized
access control software (e.g.”
eHotel” or “eAccess
”) to be managed or stored.
13..16
Enable Access
Access X
EIS1, 1bit
DPT 1.003
C,R,T
If “Access Send Mode” has been set to “Different Access” than the four (1 bit) switching
objects “Access1”...”Access 4” are visualized.
This object is sent only after a card reading acknowledge and entrance allowed.
Depending on which type or class of user has been detected during a card reading the
object “Access X” is sent.
At the same time the device sends also the object “Access Code” with the accepted
password and other access control info about card reading results.
In case “Access Send Mode” parameter is set to “Single Access” these objects are not
enabled but only the unique “Valid Access” object next is used.
17
Enable Access
Valid Access
EIS1, 1bit
DPT 1.003
C,R,T
This object is sent only after a card reading acknowledges and entrance allowed.
If “Access Send Mode” has been set to “Single Access” than only the 1 bit switching
object “Valid Access” is used to advice that the entrance has been accepted.
At the same time the device sends also the object “Access Code” with the accepted
password and other access control info about card reading results.