background image

 

P/N 387040P-

EN • REV 013 • ISS 20SEP17 

 

3 / 5 

Figure 3: Wiring diagram for NAC 

 

(1)  Signal polarity is shown when the circuit is in supervisory state. 

Polarity reverses when the circuit is active. 

(2)  Supervised. 
(3)  Power-limited unless connected to a nonpower-limited source. If 

the source is nonpower-limited, eliminate the power-limited mark 
and maintain a minimum of 0.25 in. (6.4 mm) space from power-
limited wiring. For other mounting methods, see enclosure and 
bracket installation sheets to maintain separation of power-
limited and nonpower-limited wiring. The wire size must be 
capable of handling fault current from nonpower-limited source. 

 

— or —  

 

Use type FPL, FPLR, FPLP, or permitted substitute cables, 
provided these power-limited cable conductors extending beyond 
the jacket are separated by a minimum of 0.25 in. (6.4 mm) 
space or by a nonconductive sleeve or nonconductive barrier 
from all other conductors. Refer to the NFPA 70 

National 

Electrical Code 

for more details.  

 

 

(4)  If using a G1-P Genesis series horn while connected to a 

compatible fire alarm control panel, a CDR-3 Bell Coder must 
be used to comply with NFPA 72 standard alarm evacuation 
signal. 

(5) 

47 kΩ EOLR (P/N EOL-47). 

(6)  Signaling line circuit (SLC) to next device. 
(7)  Channel 1 (ALERT) AUX riser to next module or riser 

supervisory device. 

(8)  Power-limited regulated, power supply UL/ULC Listed for fire 

protective signaling systems. 

(9)  Channel 1 (ALERT) AUX riser from previous device. 
(10)  Signaling line circuit (SLC) from previous device. Supervised 

and power-limited. 

(11)  Channel 2 (EVAC) AUX riser from previous device. 
(12)  Channel 2 (EVAC) AUX riser to next module or riser 

supervisory device. 

(5)

(1)(2)(3)(4)

+

+

+

+

(6)

(7)

(9)

(10)

+

(11)

+

(12)

Summary of Contents for SIGA-CC2

Page 1: ...s described below to configure the SIGA CC2 module See Table 1 for listing information Table 1 Personality codes Code Description UL 864 CAN ULC S527 EN 54 18 7 Riser selector supervised output Class B Personality code 7 Riser selector supervised output Class B Configures the SIGA CC2 module as a one or two input signal power 24 VDC or audio evacuation 25 or 70 VRMS riser selector The output circu...

Page 2: ...ations Each terminal on the module is limited to a single conductor Test resistors are supplied with the SIGA CC2 to prevent trouble signals on unused circuits during installation When connecting field wires remove the test resistors and install a UL ULC Listed 47 kΩEOLR at the end of the circuit The module does not support conventional smoke detectors Riser wiring notes For maximum line impedance...

Page 3: ...conductors extending beyond the jacket are separated by a minimum of 0 25 in 6 4 mm space or by a nonconductive sleeve or nonconductive barrier from all other conductors Refer to the NFPA 70 National Electrical Code for more details 4 If using a G1 P Genesis series horn while connected to a compatible fire alarm control panel a CDR 3 Bell Coder must be used to comply with NFPA 72 standard alarm ev...

Page 4: ...tted substitute cables provided these power limited cable conductors extending beyond the jacket are separated by a minimum of 0 25 in 6 4 mm space or by a nonconductive sleeve or nonconductive barrier from all other conductors Refer to the NFPA 70 National Electrical Code for more details 4 Unshielded twisted pair 5 47 kΩ EOLR P N EOL 47 6 Signaling line circuit SLC to next device 7 Channel 1 ALE...

Page 5: ...x with a dual gang cover Wire size 12 to 18 AWG 1 0 to 4 0 mm Operating environment Temperature Relative humidity 32 to 120 F 0 to 49 C 0 to 93 noncondensing Storage temperature range 4 to 140 F 20 to 60 C Regulatory information FCC compliance This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and...

Reviews: