Edwards iH1000 Instruction Manual Download Page 24

A590-00-880 Issue D

Page 18

© Edwards Limited 2008. All rights reserved.

Edwards and the Edwards logo are trademarks of Edwards Limited.

Installation

3.6.2

Gas purges

Switch on the inert gas purge to remove air from the pump and the exhaust pipeline before the process starts. Switch 
off the purge flow at the end of the process only after the remaining flammable gases or vapours have been purged 
from the exhaust pipeline.

If liquids that produce flammable vapours could be present in the pump foreline, then the inert gas purge to the dry 
pumping system should be left on all the time this liquid is present. Flammable liquids could be present in the foreline 
as a result of condensation or may be carried over from the process. 

When calculating the flow rate of inert gas required for dilution, consider the maximum flow rate for the flammable 
gases/vapours that could occur. For example, if a mass flow controller is being used to supply flammable gases to 
the process, you should assume a flow rate for flammable gases that could arise if the mass flow controller is fully 
open. 

Continually measure the inert gas flow rate: if the flow rate falls below that required, then the flow of flammable 
gases or vapours to the pump must be stopped.

3.7

Leak-test the system

Note:

If you need further information on leak-testing, look it up on the Web using URL at the start of manual, or 
contact your supplier or Edwards for advice.

Refer to 

Figure 5

, items 6 or 7.

3.8

Electrical supply

WARNING

If you use inert gas purges to dilute dangerous gases to a safe level, ensure that the pump is shut 
down if an inert gas supply fails.

WARNING

Leak test the system after installation and seal any leaks found to prevent leakage of dangerous 
substances out of the system and leakage of air into the system.

WARNING

This equipment is suitable for Installation Category II as defined in IEC 60664-3. Connect the 
system to the electrical supply through a suitably rated isolator/connector for your dry pumping 
system. (Refer to 

Table 6

).

WARNING

Ensure that the system and your electrical supply cable are suitably protected against earth 
(ground) faults and that the earth (ground) conductor of the electrical supply cable is longer than 
the phase conductors in the connector. You must fit a second protective earth (ground) conductor 
(with a cross-sectional area at least equal to phase conductor size) to the protective earth (ground) 
stud.

WARNING

All connections to the interface control must be double insulated or have equivalent protection. 
Do not connect voltages greater than 30 V a.c. or 60 V d.c. to the control/interface connections. 
If you do, the interface control will not provide protection against electric shock.

Summary of Contents for iH1000

Page 1: ...00 xxx iH160 A590 10 xxx iH160HTX A590 12 xxx iH600 A590 20 xxx iH1000 A590 30 xxx iH1800 A590 40 xxx iH1800HTX A590 42 xxx iH1800NRV A590 50 xxx iH1800NRV HTX A590 52 xxx Where xxx is as follows 460...

Page 2: ...conformity with the following standard s or other normative document s EN1012 2 1996 A1 2009 Compressors and Vacuum Pumps Safety Requirements Vacuum Pumps EN61010 1 2001 Safety Requirements for Electr...

Page 3: ......

Page 4: ...This page has been intentionally left blank...

Page 5: ...materials 17 3 6 2 Gas purges 18 3 7 Leak test the system 18 3 8 Electrical supply 18 3 8 1 Reconfigure the iH system for your electrical supply if necessary 19 3 8 2 Reconfigure the iH system for you...

Page 6: ...of pump 5 6 The front panel controls 5 7 Centre of gravity and levelling foot loads 10 8 System arrangement to reduce effective footprint if required 14 9 Reconfigure the iH system for your electrical...

Page 7: ...e instructions The use of WARNINGS and CAUTIONS is defined below CAUTION Cautions are given where failure to observe the instruction could result in damage to the equipment associated equipment and or...

Page 8: ...by contacting Edwards 1 2 Applications If you use the iH system on an application for which it is not suitable refer to Figure 1 you may invalidate your warranties If in doubt contact Edwards who will...

Page 9: ...d exhaust purge 1 3 2 The iH NRV systems For Flat Panel Display processes 1 4 Priority of control The system can be controlled by a number of modules the Pump Display Terminal PDT from the tool throug...

Page 10: ...4 Seismic bracket 4 off 5 RF earth ground stud M6 6 Cooling water return connection 7 Levelling feet 4 off 8 Nitrogen purge port 9 Castor 4 off 10 Exhaust enclosure 11 Active gauge connection 12 iTIM...

Page 11: ...p Figure 6 The front panel controls 1 Inverter 2 Extraction port 3 Lifting eyebolts 2 off 4 RF earth ground cable iH160 1000 1800 only 5 Pumped gas inlet connection 6 Leak test port combination 7 Leak...

Page 12: ...A590 00 880 Issue D Page 6 Edwards Limited 2008 All rights reserved Edwards and the Edwards logo are trademarks of Edwards Limited This page has been intentionally left blank...

Page 13: ...ial force to push the pump 8 16 20 kg Sustained force to push the pump 5 7 8 kg Earth leakage 1 1 1 1 3 mA Warm up time to nominal pumping performance 15 15 15 minutes Minimum warm up time to process...

Page 14: ...imum warm up time to process gas pumping 4 4 hours Performance 50 Hz 60 Hz Typical peak pumping speed 165 1800 m3 h 1 Ultimate shaft seal purge only 1x10 2 1x10 3 mbar Maximum inlet pressure Atmospher...

Page 15: ...Max power input to both motors kW 6 51 7 8 7 8 iH1800 HCDP Full load Amp 14 4 14 9 14 4 Motor rating kW 2 9 3 5 3 5 HCMB Full load Amp 14 4 14 9 14 4 Motor rating kW 2 9 3 5 3 5 Max power input to bot...

Page 16: ...7 Centre of gravity and levelling foot loads Table 4 Centre of gravity and levelling foot loads Refer to Figure 7 iH80 iH600 iH1000 iH160 iH1800 Centre of gravity A 661 661 661 661 661 B 322 309 314 3...

Page 17: ...twork LON communications connector XLR type 4 way plug 24 V d c 0 75 A Exhaust gas management interface DIN type 6 pin plug 1 normally open and 3 common 30 V a c 1 A 2 normally open and 4 normally clo...

Page 18: ...erature range 10 30 C Typical pressure differential across supply and return With cooling water supply temperature of 20 C and flow rate of 3 l min 1 15 psig Water type Treated or non corrosive indust...

Page 19: ...tem from the electrical supply so that they cannot be operated accidentally z Electrical nitrogen and water supplies are all potentially hazardous energy sources Before carrying out any maintenance th...

Page 20: ...ncern suitable vibration isolators not supplied should be fitted between the docking points and the bolt or stud if doing this the levelling feet will need to be removed 4 If preferred the lifting eye...

Page 21: ...e HCDP pump and the HMB pump are correct If a pump oil level is incorrect pump performance may be affected and the pump may be damaged The iH system is given a charge of oil before it leaves the facto...

Page 22: ...ressure z On very dusty applications use a low impedance inlet filter to minimise damage to the pump z The exhaust pipelines should be suitable for 150 C for HTX systems 1 Remove the temporary cover o...

Page 23: ...equipment you must z Not allow air to enter the equipment z Ensure that the system is leak tight z Ensure that pumped gases do not enter their flammable range This can be achieved by diluting flammabl...

Page 24: ...ak test the system Note If you need further information on leak testing look it up on the Web using URL at the start of manual or contact your supplier or Edwards for advice Refer to Figure 5 items 6...

Page 25: ...ecure with the two screws 2 3 8 2 Reconfigure the iH system for your electrical supply iH80 600 only If you want to use an iH80 or iH600 system with a different electrical supply use the following pro...

Page 26: ...ll rights reserved Edwards and the Edwards logo are trademarks of Edwards Limited Installation Figure 9 Reconfigure the iH system for your electrical supply 1 Cover 2 Screw 2 off 3 Electrics box 4 Com...

Page 27: ...ed for use in domestic buildings or in properties directly connected to an electrical supply network which also supplies domestic buildings CAUTION Do not connect voltages greater than specified in Ta...

Page 28: ...dentally dragged and the strain relief bush on the electrical supply connector mating half fails the earth ground conductor will be the last conductor to be pulled from the connector 1 Refer to Figure...

Page 29: ...earth ground stud Figure 3 item 5 You must use a suitable low impedance cable for example use braided cable 3 10 Connect to your emergency stop circuit Note If you do not connect to your own control e...

Page 30: ...ooling water outlet Figure 3 item 6 and connect your water supply hose to the cooling water inlet Figure 3 item 3 4 Turn on the cooling water supply 5 Inspect the water hoses pipelines and connections...

Page 31: ...s or refer to the Web 8 Look at the pressure gauge in your inlet pipeline z If the pressure is increasing the HCDP pump motor terminal box and or if you have an iH160 1000 or 1800 system the HMB pump...

Page 32: ...sage will be shown on the Pump Display Terminal if fitted and will be sent to the Interface Module s connected to the iH system Ensure that your installation is configured so that it remains safe if t...

Page 33: ...e PDT or the IM iTIM and IM operation 4 Use your control equipment to set the pump start stop signal to the interface connector and check that the Running LED is illuminated z Control must be taken wi...

Page 34: ...e interface connector The Running LED Figure 6 item 2 will then go off and the pump running status output signal will open PDT operation CAUTION If you stop the pump without the nitrogen purge cycle i...

Page 35: ...ers 810 and 812 z HMB PHASE IMBALANCE error number 1012 On an iH160 1000 or 1800 system the following alarms will cause only the HMB pump to shut down whether run til crash is selected or not z HMB CU...

Page 36: ...CTIVATED If connected z The Running LED will go off z The Alarm LED illuminates 4 7 Restart the pump after an emergency stop or automatic shut down Note If the iH system has automatically shut down be...

Page 37: ...leshooting inside electrical enclosures These enclosures contain hazardous voltages and are not operator areas WARNING Leak test the system after maintenance and seal any leaks found to prevent leakag...

Page 38: ...etails The iH system requires little user maintenance Safety sensors fitted to the iH system do not require routine maintenance The maintenance operations you can carry out are described in the follow...

Page 39: ...5 If necessary disconnect the iH air extraction port from your factory extraction system 6 If necessary disconnect any accessories from the iH system 7 Adjust the levelling feet so that the iH system...

Page 40: ...ating in the fuse holder Refer to Table 6 for the fuse ratings Refit the fuse holder in the Electrics Box then use a flat bladed screwdriver to turn the fuse holder clockwise by a 1 4 of a turn to sec...

Page 41: ...scribed in Section 3 of this manual 6 3 Disposal Edwards products are supported by a world wide network of Edwards Service Centres Each Service Centre offers a wide range of options including disposal...

Page 42: ...A590 00 880 Issue D Page 36 Edwards Limited 2008 All rights reserved Edwards and the Edwards logo are trademarks of Edwards Limited This page has been intentionally left blank...

Page 43: ...tor When you order please state for each part required z Model and Item Number of your equipment z Serial number if any z Item Number and description of the part 7 2 Service Edwards products are suppo...

Page 44: ...USA D372 18 200 Laptop Europe D372 18 300 Laptop UK D372 18 400 Laptop Japan D372 18 500 PCMCIA Laptop D372 17 000 Nitrogen flow switch A532 54 000 IH Disconnect box U20000445 IH Photohelic switch ga...

Reviews: