PRODUCT DESCRIPTION
The routing of power-limited and nonpower-limited wiring differs with
each cabinet. For more information on the routing of power-limited and
nonpower-limited wiring, see the cabinet’s installation sheet.
SPECIFICATIONS
DATE: 22AUG00
INSTALLATION SHEET:
INSTALLATION SHEET P/N: 387472
FILE NAME: 387472.cdr
REVISION LEVEL: 2.0
CREATED BY: B. Graham
APPROVED BY: K. Johnson
2-MCMN
Network Main Controller Module
Wire Stripping Guide
1/4 inch (6.4 mm)
Strip 1/4 inch from the ends of ALL wires that connect to the terminal
blocks of the module.
Caution:
Exposing
than 1/4 inch of wire may cause a ground fault.
Exposing
than 1/4 inch of wire may result in a faulty connection.
more
less
Warning!
Disconnect power to cabinets before installing or removing
components. Failure to do so may result in serious injury or loss of
life.
WIRE ROUTING
!
Caution!
Observe static-sensitive material handling practices.
PRODUCT DIAGRAM
EDWARDS SYSTEMS TECHNOLOGY, INC.
SARASOTA, FL: 941-739-4300 FAX 941-753-1806
CHESHIRE, CT: 203-699-3000 FAX 203-699-3075
OWEN SOUND, CANADA: 519-376-2430 FAX 519-376-7258
INTERNATIONAL, CANADA: 905-270-1711 FAX 905-270-9553
Input Power
Ground Fault Detection
RS-485 NET Terminal
*
*Note:
RS-485 ANN Terminal
*
*Note:
RS-232 Terminal
NACs
SDC
Relay Contacts
Environmental Conditions
24 Vdc @ 147 mA, standby; 216 mA active
10 k
to earth, all field wiring except
common relay contacts
Max. Line Capacity
10 nodes
Max. Line Impedance
0.44 f/100
Max. Wire Size
14 AWG (1.5 mm )
five 2-MCMN and five 2-CPU
Max. Line Capacity
30 addresses
Max. Line Impedance
0.44 f/100
Max. Wire Size
14 AWG (1.5 mm )
SAN annunciators, 2-LSRAs, and 2-SMDNs.
Non-isolated, 50 ft. (15.2 m) max.
Must be located in the same room.
Quantity/Style
Two Class A (Style 6) or Class B (Style 4)
Voltage
24 Vdc, Nominal
Available NAC Current
3.5 A for all NACs
NAC Current Rating
3.5 A or 100 W @ 25/70 Vrms per circuit
EOL Resistor
15 K
, ½ W
Maximum Wire Size
12 AWG (2.5 mm )
Class (Style)
Class A (Style 7) or Class B (Style 4)
Detector Capacity
96 Signature Series detectors
Module Capacity
94 Signature Series modules
Line Resistance
65
max. full load
Line Capacitance
0.33 f, max.
Maximum Wire Size
14 AWG (1.5 mm )
Alarm and Trouble
Form C, rated at 24 Vdc nominal @ 1 A
Supervisory
Form A, rated at 24 Vdc nominal @ 1 A
Temperature Range
32 to 100 °F (0 to 38 °C)
Humidity
93%, Non-condensing
W
m
W
m
W
W
W
m
2
2
2
2
s
s
The Network Main Controller Module (MCMN) is the foundation of
the network and contains the principal microprocessor and controls
for the fire alarm system.
The MCMN has a dual-purpose RS-485 port. The network
terminals (NET) provide Class A (Style 6) or Class B (Style 4)
communications for the network. The annunciator terminals (ANN)
provide communications with 2-LSRAs, 2-SMDNs, and SAN
Annunciators.
The MCMN also has an RS-232 port to provide communications
for printers. An RJ-11 jack provides a means for downloading
programmed data from an IBM compatible computer to the MCMN.
All external connections are transient-protected.
The MCMN provides one multiplexed Signature Data Circuit (SDC)
and two Notification Appliance Circuits (NACs). The SDC and the
NACs can both operate on Class A or Class B wiring. The SDC
can support 96 Signature Series detectors and 94 Signature
Series modules. The NACs have separate input terminals, which
are rated at 24 Vdc @ 3.5 A or 100 W @ 25 Vrms or 70 Vrms
audio. The NAC terminals may share power or receive it from an
external source.
During alarm, supervisory, and trouble conditions the MCMN relay
contacts close to report the off-normal conditions. There are two
Form C relays and a Form A relay. The Form C relays handle
alarm and trouble conditions and operate on 24 Vdc, nominal @ 1
A. The Form A relay handles supervisory conditions and operates
on 24 Vdc, nominal @ 1 A.
Related documentation: Network Supplement Manual
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for EST2
Page 18: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 22: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 24: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 28: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 58: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 64: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 66: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 80: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 88: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 90: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 92: ...Technical Manuals Online http www tech man com firealarmresources com ...