S9
S10
S10
S9
SWU-8(/3)
Group number
Output addresses S1 dip switch settings
Module
1
2
3
4
1
01-08
on
off
off
off
2-SANCOM
2
09-16
off
on
off
off
SHO-4
3
17-24
on
on
off
off
SLU-16
4
25-32
off
off
on
off
SLU-16
5
33-40
on
off
on
off
SWU-8(/3)
6
41-48
off
on
on
off
SWU-8(/3)
7
49-56
on
on
on
off
8
57-64
off
off
off
on
9
65-72
on
off
off
on
10
73-80
off
on
off
on
11
81-88
on
on
off
on
12
89-96
off
off
on
on
Group number
Input addresses
S1 dip switch settings
Module
1
2
3
4
1
01-08
on
off
off
off
2-SANCOM
2
09-16
off
on
off
off
SHO-4
3
17-24
on
on
off
off
SWU-8(/3)
4
25-32
off
off
on
off
SWU-8/3
5
33-40
on
off
on
off
6
41-48
off
on
on
off
7
49-56
on
on
on
off
8
57-64
off
off
off
on
9
65-72
on
off
off
on
10
73-80
off
on
off
on
11
81-88
on
on
off
on
12
89-96
off
off
on
on
ON
ON
1
1
2
2
3
3
4
4
To set the dip switches:
A.
Configure the SAN-CPU in the system programming utility.
B.
Note the
SWU-8(/3) in the programming utility (09 to 81).
C.
Set the dip switches on S9 and S10 to match the group numbers of the SWU-8’s start input and start output addresses.
start input and output addresses of the
Set the dip switches.
3
Remember that the SWU-8:
Cannot occupy the 2-SANCOM addresses (01 through 09).
Requires one input address group and two output address groups,
which consist of eight addresses each.
Remember that the SWU-8/3:
Cannot occupy the 2-SANCOM addresses (01 through 09).
Requires two input address groups and two output address groups,
which consist of eight addresses each.
INSTALLATION
In this example, the
start address is 17
and the dip switch is
set to a binary 3.
Note: The SWU-8
only requires
addresses 17 to 24.
In this example, the
start address is 33
and the dip switch is
set to a binary 5.
To label the SWU-8(/3):
A.
Identify each LED/switch group on the SWU-8(/3) according to its programmed function.
B.
Write the functions on the slip-in legend sheet next to the appropriate LED/switch group.
C.
Insert the label under the SWU-8(/3) face plate.
4 Label the SWU-8(/3).
Slip-in label
Make the ribbon cable connections.
2
JP1
JB1
P1
P1
P1
P1
P2
P2
P2
P2
2-SANCOM
From P1
on the
SAN-CPU
SLU-16
SWU-8(/3)
SHO-4
A.
Plug the ribbon cable assembly (P/N 250080) from P1 of the SAN-CPU into P2 of the 2-SANCOM.
B.
Plug the ribbon cable from P1 of the 2-SANCOM to P2 of the next SAN series module.
C.
Plug the ribbon cable from P1 of each SAN module to P2 of the next SAN module until you reach the last one.
D.
Install the continuity jumper on the last SAN module.
Note: If the SWU-8(/3) is the last module, install the continuity jumper on JP1.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for EST2
Page 18: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 22: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 24: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 28: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 58: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 64: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 66: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 80: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 88: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 90: ...Technical Manuals Online http www tech man com firealarmresources com ...
Page 92: ...Technical Manuals Online http www tech man com firealarmresources com ...