background image

CMU 100 - RS485 to Singlemode Fiber Optic Converter

bit/s

Switch

115200

38400

2400

ON

OFF

OFF

BAUD rate  setting  19,2 kbit/s is valid for  all  standard  communication  protocols,  that do  not 
request   special  timings.   If   special  protocols   (small  request-respond  time   required)   are   used 
please note it in order.

NOTE!   If   there   are   problems   with   communication,   try   using   higher   speed   setting.   Some 
manufacturer   have   different   markings   for   B   and   A  line.   Try   to   switch   A  and   B   wires.   See  

http://en.wikipedia.org/wiki/RS-485

 for detailed information.

Connector pin table

MSTB

1

2

3

Description

GND

- (B)

+ (A)

Page:

Company:

Device:  

Document: 

Code:

Date:

10

Ediseja 21 CMU 100 / 1.5.S - 0

User manual CMUMU15S

01.09.2019

Picture 5: RS485 interface board appearance with switch settings

Summary of Contents for CMU 100 Series

Page 1: ...7 5 S 0 CMU 100 1 5 T 0 CMU 100 7 5 T 0 CMU 100 1 5 U 0 CMU 100 7 5 U 0 Company Device Document Code Date Ediseja 21 CMU 100 1 5 S 0 User manual CMUMU15S 01 09 2019 CMU 100 RS485 to Singlemode Fiber Optic Converter User Manual ...

Page 2: ...ICATION 7 3 3 APPEARANCE 8 3 4 HARDWARE DESCRIPTION 8 3 4 1 MAIN BOARD 8 3 4 2 RS485 INTERFACE BOARD 8 3 4 3 SINGLEMODE FIBER OPTIC INTERFACE BOARD 11 4 SCHEMATIC 12 5 INSTALLATION 13 5 1 INSTALLATION 13 6 COMMISSIONING MAINTENACE 15 6 1 COMMISSIONING 15 6 2 MAINTENANCE 15 7 TECHNICAL DATA 16 8 DIMENSIONS 18 9 ORDERING 19 Page Company Device Document Code Date 2 Ediseja 21 CMU 100 1 5 S 0 User man...

Page 3: ...tegne 21C 1000 Ljubljana Slovenia EU Tel 00 386 51 643 411 051 643 411 Email grega flander ediseja21 com www ediseja21 com Copyright Copyright Ediseja 21 2019 All rights reserved Explanation of the symbols Read the instructions Device was tested with 2 5 kV AC voltage to check the device insulation Device ground terminal Waste Electrical and Electronic Equipment WEEE Directive 2002 96 EC the affix...

Page 4: ... the device during operation Disregarding of safety rules can result in severe personal injury or property damage Only qualified personnel may work with described devices after being familiar with warnings and safety notices in this paper and other safety regulations Warning Device must operate completely assembled Device must be used as described No modifications of the device should be made Warn...

Page 5: ...re s task is switching between communication ports and allows almost any combination between them 2 1 2 HARDWARE Hardware is based on main board with power supply and port switching logic On that board interface boards are attached CMU 100 can handle up to 8 different interface boards Currently available interface boards RS232 isolated RS485 Multimode Fiber Optic with ST and SMA connectors Singlem...

Page 6: ...CMU 100 RS485 to Singlemode Fiber Optic Converter Page Company Device Document Code Date 6 Ediseja 21 CMU 100 1 5 S 0 User manual CMUMU15S 01 09 2019 Picture 1 CMU 100 system general diagram ...

Page 7: ...nection to all common station batteries Additionaly it can be also connected to standard AC voltages This device is intended for use in cubicles and cabinets in all kinds of power production transmission and distribution stations It requires no maintenace All normaly used connectors switches and light indicators are accessed at the front side of the device One light indicator indicates power suppl...

Page 8: ...ive Rx line and the left one shows activity on transmit Tx line Ports Configuration Port 1 2 Interface RS485 FO SM 3 4 2 RS485 INTERFACE BOARD Description Single galvanically isolated half duplex RS485 port with Phoenix 3 pin screw connector with automatic switch to receive after end of transmission and with additional terminating and stabilizating resistors Hardware settings For proper functionin...

Page 9: ...no voltage difference between those pins and some device do not work correctly On this port board so called true fail safe RS485 chip is used so board works correctly without stabilisation at invalid RS485 bus state But still switches for stabilisation are provided on port board The stabilization on RS485 bus may be set on one device only Switches at the lower side of connector Switch 4 5 6 Descri...

Page 10: ...used please note it in order NOTE If there are problems with communication try using higher speed setting Some manufacturer have different markings for B and A line Try to switch A and B wires See http en wikipedia org wiki RS 485 for detailed information Connector pin table MSTB 1 2 3 Description GND B A Page Company Device Document Code Date 10 Ediseja 21 CMU 100 1 5 S 0 User manual CMUMU15S 01 ...

Page 11: ...0 km Signal detect LED is activated when receiver receives enough light signal from transmitter from another end of the fiber cable Warning Radiation emitted by single mode laser devices can be dangerous to human eyes Avoid eye exposure to direct or indirect radiation Company Device Document Code Date Page Ediseja 21 CMU 100 1 5 S 0 User manual CMUMU15S 01 09 2019 11 Picture 6 Standard data rate v...

Page 12: ...CMU 100 RS485 to Singlemode Fiber Optic Converter 4 SCHEMATIC Page Company Device Document Code Date 12 Ediseja 21 CMU 100 1 5 S 0 User manual CMUMU15S 01 09 2019 Picture 8 General diagram ...

Page 13: ...operating temperature must be observed Check the device for damage at unpacking If device is damaged it must not be installed but it should be send to the manufacturer for repair The device should not be opened The device should be mounted on a 35 mm rail acc to EN 50022 Attach ground wire before attaching power supply Device must be grounded during operation Single core or stranded wire 0 5 2 5 m...

Page 14: ...CMU 100 RS485 to Singlemode Fiber Optic Converter Page Company Device Document Code Date 14 Ediseja 21 CMU 100 1 5 S 0 User manual CMUMU15S 01 09 2019 Picture 9 left installation right deinstallation ...

Page 15: ...e completely assembled Device must be used as described No modifications of the device should be made Attach ground wire before attaching power supply Device must be grounded during operation Check if the power supply voltage complies with device operation voltage Do not open device while it is energized Hazardous voltage is present inside the device If single mode fiber optic interface is used do...

Page 16: ...wer Supply Wire crossection 0 5 2 5 mm2 type single or stranded wire voltage rating 500 V colour see valid standard Ground wire crossection Cu 2 5 mm2 colour see valid standard Communication port RS485 interface type 5 M L Type RS485 Direction half duplex Speed Interface type 5 19 2 115 2 kbit s Interface type M 4 8 38 4 kbit s Interface type L 300 2400 bit s Distance up to 1200 m Isolation 1000 V...

Page 17: ... 1 transmitter Distance up to 20 km Connector type CMU 100 x x S SC CMU 100 x x T FC CMU 100 x x U ST slowest interface defines device s maximum speed Other data Weight approx 0 3 kg Dimensions see picture H D W 105 mm 111 mm connectors 40 mm Temperature range 0 C to 55 C Humidity operating up to 95 noncondensing Enclosure Material Al IP 20 Mount type standard DIN 35 rail acc to DIN EN 50022 Class...

Page 18: ...CMU 100 RS485 to Singlemode Fiber Optic Converter 8 DIMENSIONS Page Company Device Document Code Date 18 Ediseja 21 CMU 100 1 5 S 0 User manual CMUMU15S 01 09 2019 Picture 10 Dimensions ...

Page 19: ...p to 2 048 Mbit s 500 m 6 Multimode 820 nm fiber optic with SMA connector up to 2 048 Mbit s 500 m 7 Singlemode 1310 nm fiber optic with SC connector up to 2 048 Mbit s 20 km S Singlemode 1310 nm fiber optic with FC connector up to 2 048 Mbit s 20 km T Singlemode 1310 nm fiber optic with ST connector up to 2 048 Mbit s 20 km U USB one virtual com port 8 Ethernet 10 100Base TX port server with one ...

Page 20: ...048 Mbit s high voltage power supply CMU 100 1 6 S 0 FO MM FO SM FC connector 20 km up to 2 048 Mbit s high voltage power supply CMU 100 1 6 T 0 FO MM FO SM ST connector 20 km up to 2 048 Mbit s high voltage power supply CMU 100 1 6 U 0 FO MM ETH 500 m 820 nm 10 100 Mbit s virtual com port high voltage power supply CMU 100 1 6 9 0 ETH TX ETH FX 100 Mbit s 1300 nm 2000 m range high voltage power su...

Page 21: ... to 6 x RS232 CMU 100 2 5 1 1 1 1 1 1 12 7 x RS232 RS485 to 7 x RS232 CMU 100 2 5 1 1 1 1 1 1 1 12 2 x FO MM RS485 to 2 x multimode fiber optic CMU 100 2 5 6 6 12 3 x FO MM RS485 to 3 x multimode fiber optic CMU 100 2 5 6 6 6 12 4 x FO MM RS485 to 4 x multimode fiber optic CMU 100 2 5 6 6 6 6 12 5 x FO MM RS485 to 5 x multimode fiber optic CMU 100 2 5 6 6 6 6 6 12 6 x FO MM RS485 to 6 x multimode ...

Page 22: ... 6 6 6 6 6 6 5 RS232 FO MM 6 x FO MM 8 channel star coupler RS232 multimode fiber optic to 6 x multimode fiber optic high voltage power supply CMU 100 2 1 6 6 6 6 6 6 6 5 4 xFO MM 4x RS232 4 channel converter multimode fiber optic to RS232 high voltage power supply CMU 100 2 6 6 6 6 1 1 1 1 7 Contact Ediseja 21 razvoj elektronskih naprav d o o Stegne 21C 1000 Ljubljana Slovenia EU Tel 00 386 51 64...

Reviews: